88 Example 7: Configuring the process data read from the drive PROFIBUS Parameter 916 can be used to define which data is read cyclically from the drive as application-specific process data. In the example below, drive parameter 1.04 (01h.04h) is selected to be transmitted by the drive as PZD3. The selection is in force until it is superseded by another selection. Subindex (IND) defines which process data word the required data is transmitted in, and Parameter Value defines which drive parameter is mapped to that word. Request (Change parameter value [array]) Parameter Number (916 decimal) Subindex (03 = PZD3)* Parameter Value CW REF PZD3 PZD4 PZD5 PZD6 DP 73 94 03 00 00 00 01 04 04 7F 34 15 00 00 00 00 00 00 00 00 DP Resp header 43 94 03 00 00 00 01 04 03 37 34 15 00 00 00 00 00 00 00 00 trailer Req SW ACT PZD3 PZD4 PZD5 PZD6 Parameter Value Subindex (03 = PZD3)* Parameter Number (916 decimal) Response (Transfer parameter value [array]) *2nd byte reserved Subsequent response frames: Resp DP DP xx xx xx xx xx xx xx xx xx xx xx xx 00 0B xx xx xx xx xx xx header trailer PZD3 (Value of drive parameter 1.04) Communication