Appendix E: Level transducer block
00809-0100-4026, Rev HA
November 2014
Table E-12. Level Rate
Value
Display
Description
0
Default
1061
1063
1067
1069
M/s
M/h
Ft/s
In/m
Unit for LCD is the same as set in the value
window
Meter per second
Meter per hour
Feet per second
Inch per minute
(1)
(1) Default only for parameter LCD_VELOCITY_UNIT.
Table E-13. Temperature
Value
Display
Description
0(1)
Default
1001
1002
°C
°F
Unit for LCD is the same as set in the value
window
Degree Celsius
Degree Fahrenheit
(1) Default only for parameter LCD_TEMPERATURE_UNIT.
Table E-14. Signal Strength
Value
Display
Description
1243
mV
millivolt
Value
Display
Description
0(1)
Default
1034
1038
1042
1043
1044
1048
1049
1051
M3
L
In3
Ft3
Yd3
Gallon
ImpGall
Bbl
Unit for LCD is the same as set in the value
window
Cubic meter
Liter
Cubic Inch
Cubic feet
Cubic yard
US gallon
Imperial gallon
Barrel (oil)
Table E-15. Volume
(1) Default only for parameter LCD_VOLUME_UNIT.
E.4
Diagnostics device errors
In addition to the BLOCK_ERR and XD_ERROR parameters, more detailed information on the
measurement status can be obtained via SENSOR_DIAGNOSTICS. Table H-1 on page 282 lists
the potential errors and the possible corrective actions for the given values. The corrective
actions are in order of increasing system level compromises. The first step should always be to
reset the gauge and then if the error persists, try the steps in Table H-1. Start with the first
corrective action and then try the second.