Modbus/TCP 7-4 Bit Addressing Examples • To reference the first bit of the Input Table use Input Status bit address 16. • To reference the 15th bit of the Input Table use Input Status bit address 2 • To reference the first bit of the Output Table use Coil bit address 16400. • To reference the 15th bit of the Output Table use Coil bit address 16386. Word Addressing Examples • To reference the first word of the Input Table use Input Register address 1. • To reference the 10th word of the Input Table use Input Register address 10 • To reference the first word of the Output Table use Holding Register address 1025. • To reference the 100th word of the Output Table use Holding Register address 1124. © 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014