TEMPERATURE Setup (Point Temperature, Point Thermistor) [Devicen] - Section name. Address - serial number of the sensor. DeviceType - Device type. (DeviceType=TEMP) PollTime - the transmit interval of the sensor. (ms) Label - Name used for the device (and Topic). Log - Enable/disable logging of device. LogDecimalPlaces - Number of decimals to create when logging. Units - See DDE variables list under input.units for description. Cal1Raw - Two point calibration point 1. Cal2Raw - Two point calibration point 2. Cal1Engr - Two point calibration engineering units for point 1. Cal2Engr - Two point calibration engineering units for point 2. DeadBand - Dead band filtering value in ºC. (Default 0.01) FilterElements - running macro filter of the sampled data. Syntax: [no. of elements, type] where no. of elements is number of samples to filter; type – “AVERAGE”, “MEDIAN” and “AVERAGEMEDIAN”. Default is “=0,MEDIAN” – no filtering. Example: FilterElements=6,AVERAGE Description - General purpose description. CorrID – What CorrectionID to use with this device. Must be found in the "Correction.INI" file that you write and keep in the same directory as the OneSix.ini file. 0 is the default and means no correction; 127 is the maximum OneSix Server Help OneSix Server .ini File Format x 17