Table 7-1.
TEST
OPERATING TESTS
MIL-STD-705
PROCEDURE
TEST PARAMETER
1.
Regulator and governor stability and
transient response. (Short Term).
608.1a
See tables 7-2 and 7-3.
2.
Overspeed protection device.
505.2a
2400 rpm to 2450 rpm.
3.
Phase balance.
508. 1C
See tables 7-2 and 7-3.
4.
Circuit interrupter (Short Circuit).
512.lc
Instantaneously at 425
± 25 percent of rated
current.
5.
Circuit interrupter (Overload Trip).
512.2c
8 ± 2 minutes at 130
percent of rated
current.
6.
Circuit interrupter (Undervoltage).
(Class 1 sets only).
512.3c
Instantaneously below
48 volts, 6 ± 2 seconds
at 99 + 24 volts or less.
7.
Circuit interrupter (Overvoltage).
512.3c
Not more than 1 second
after voltage has risen
to and remained at any
value greater than 153
± 3 volts for not less
than 200 milliseconds.
8.
Circuit interrupter (Under Frequency
Trip).
514.1
60 Hz = 55 ± 1
50 Hz = 46 ± 1
400 Hz = 370 ± 5
9.
Low oil pressure protective device.
515.la
Trip pressure 17 + 3 psi.
10.
Reverse power protective device.
11.
High coolant temperature protective.
12.
Low fuel protective device.
13.
Regulator range.
511.lc
Test at both 50 Hz and
60 Hz for Mode I sets.
See tables 7-2 and 7-3.
14.
Phase sequence (Rotation).
507.lc
Ll, L2, L3.
15.
Frequency adjustment range.
511.2b
See tables 7-2 and 7-3.
16.
Parallel operation provisions.
Refer to paragraph 7-10.
17.
Malfunction indicator system.
Refer to paragraph 7-12.
18.
Maximum power.
a.
30kW, 50/60 Hz, TU and TP 42.2kW
b.
30kW, 400 Hz, TU 24.2 kW
Refer to paragraph 7-8.
515.2a
Trip temperature ±222
± 3°F.
Refer to paragraph 7-9.
640.4
CAUTION
Prior to performing any of the operating tests listed in table 7-1, insure that
the generator set is serviced with the correct fuel, oil, and coolant as listed
on the data plate.
7-3