Download DM-2 Gauge Manual
Transcript
Time averaging, seconds Actual leakage area as measured, Press [Set Pressure] Read peak pressure from gauge Read peak % speed from gauge Read final % speed from gauge 4 8 in2 60Pa 92Pa 34% 15% 4 12 in2 60Pa 83Pa 33% 18% 4 16 in2 60Pa 71Pa 32% 27% 4 20 in2 60Pa 60Pa 37% 37% 4 24 in2 60Pa 60Pa 49% 49% 4 28 in2 60Pa 60Pa 61% 61% 4 32 in2 60Pa 60Pa 76% 76% If you believe you have a more severe problem with overshoot, fill out the table below and send it to tech-support. Device [1000, 2000, 3000] Range, [C4, C2, C1] Time averaging, seconds Actual leakage area as measured, Press [Set Pressure] Read peak pressure from gauge Read peak % speed from gauge Read final % speed from gauge Set the correct Device on your gauge because it will calculate different results depending on which Device is selected. 9.10 Keep the Keep Rechargeable Batteries in top shape The DM-2 is designed to recharge NiMH batteries in the gauge, eliminating the need to purchase a stand-alone battery charger. The charging cycle is designed to fully discharge batteries before recharging them. This can cause problems if the DM-2 is connected to a power plug for only brief periods of time. If the gauge exhibits any of the following conditions, it may be a problem with the rechargeable batteries: Short battery life Will not turn on Keys will not respond Loss of power during test The solution is to reset gauge and charge the batteries, or switch to nonrechargeable batteries (remember to change the setting to tell the gauge about the switch in battery type using [Settings] to set the “Battery Type”. To charge the batteries: 1. Connect the AC power supply if rechargeable NiMH batteries are already installed. Page 52 of 72 ©Retrotec Inc. 2012