Design of Mini Multiset
3. Installation Instructions
Reference for air-discharge chamber (field supply)
Required space around outdoor unit
AES 04-05-06 MMIH) with ***
If an air discharge chamber is used, the space shown below must be secured around the outdoor unit.
If the unit is used without the required space, a protective device may activate, preventing the unit from operating.
Min. 200
Min. 1000
(1) Single-unit installation
2
Unit: mm
CAUTION
The top and both sides must remain open.
If there are obstacles to the front and rear of the outdoor unit,
the obstacle at either the front or rear must be no taller than the
height of the outdoor unit.
(2) Multiple-unit installation
More than 300
More than 300
More than 400
Installation in lateral rows (side-by-side)
More than 200
CAUTION
Unit: mm
The front and top must remain open.
The obstacles must be no taller than the height of the outdoor unit.
Installation in front-rear rows
Installation with intakes facing
intakes or outlets facing outlets
Installation with intakes facing outlets
More than 400
More than 2000
More than 1500
Unit: mm
CAUTION
The front and both sides must remain open.
2 - 28