Download Danfoss 102 Operating instructions
Transcript
Electrical Installation VLT® HVAC Drive Operating Instructions 4.8.6 RS-485 Serial Communication Up to 32 nodes can be connected as a bus, or via drop cables from a common trunk line to 1 network segment. Repeaters can divide network segments. Each repeater functions as a node within the segment in which it is installed. Each node connected within a given network must have a unique node address, across all segments. • Connect RS-485 serial communication wiring to terminals (+)68 and (-)69. • Terminate each segment at both ends, using either the termination switch (bus term on/off, see Illustration 4.13) on the frequency converters, or a biased termination resistor network. • Connect a large surface of the screen to ground, for example with a cable clamp or a conductive cable gland. • Apply potential-equalising cables to maintain the same ground potential throughout the network. • Use the same type of cable throughout the entire network to prevent impedance mismatch. Cable Screened twisted pair (STP) Impedance 120 Ω Max. cable length [m] 1200 (including drop lines) 500 station-to-station 4 4 Table 4.4 Cable Information MG11AJ02 - Rev. 2013-07-31 19