Download Viessmann GW2 Technical data
Transcript
Additional information Coding 2 (continued) Overview of all codings (continued) 5285 941 v.1.5 Coding as per Function factory setting Address: Value New coding Address: Value Possible change 88: 0 General Temperatures displayed in Celsius 88: 1 Temperatures displayed in Fahrenheit 89: 1 General Automatic participant recognition on KM-BUS 89: 0 No participant reognition 8A: 175 General Display of codings which can be set for the system type concerned 8A: 176 All codings displayed regardless of system type and equipment installed 8E: 4 General 8E: 0 Display and acknowledgment of faults: on the programming unit and 8E: 1 all Vitotrol remote controls installed Only on the programming unit of the control unit 8E: 2 On the programming unit of the control unit and on the remote control for mixing valve circuit M2 8E: 3 On the programming unit of the control unit and on the remote control for mixing valve circuit M3 On the programming unit of the control unit and on the remote control for system circuit A1 90: 128 General Time constant for calculating the outdoor temperature change 21.3 hours 90: 0 to 90: 199 Fast matching (lower values) or slow matching (higher values) of the supply temperature to the change in the outdoor temperature according to the selected value; 1 increment = 10 minutes 91: 0 General Without changeover of the heating program 91: 1 91: 2 With changeover of the heating program (connection via plug aVD): Changeover effective for: System circuit A1 Mixing valve circuit M2 91: 3 System circuit A1 and mixing valve circuit M2 91: 4 Mixing valve circuit M3 91: 5 System circuit A1 and mixing valve circuit M3 91: 6 Mixing valve circuits M2 and M3 91: 7 All heating circuits (A1, M2, M3) 93: 1 Central fault indication in emissions test mode/service display effective for central fault 92: 165 General Do not adjust! Will only display if coding address “8A: 176” is set Central fault indication in emissions test mode/service display not effective for central fault 93: 0 General 94: 0 General Without plug-in adaptor for external safety equipment 94: 1 With plug-in adaptor for external safety equipment; recognized automatically 96: 1 General With mixing valve extension circuit board 96: 0 Without mixing valve extension circuit board 125