Download Simrad AP50 Installation manual
Transcript
Simrad AP50 Autopilot Thruster Drive (Only applicable for Continuous and Danfoss thrusters) For On/Off thrusters, it is important to keep thruster activity to a minimum. TI51 therefore has a feature that adaptively adjusts the length of each thruster command to bring the vessel back on heading without over- or undershoot. When setting Thruster drive to “Adaptive on/off”, this feature will also apply for continuously type thrusters in all Work modes (not Follow Up). For operations where the Thruster sens can be of some degrees, on/off adaptively will reduce activity also for continuous type thrusters. Refer also to the Thruster gain setting for optional performance. Default: Continuous Response delay (Only applicable for Continuous and Danfoss thrusters) This parameter determines the slope-time of the start/stop signal to the thruster. Increased value will give softer start/stop and less wear of the thruster. Big powerful thrusters normally need a longer start time than small rapid thrusters. Range: 0-2 seconds Default: 1 second 88 20222469 / B