Typical Switch Hookup Detail MAC-4R Control Panel Notes: 1. All switch inputs are shown open and assumed to be held closed for secure state. 2. Total wire resistance should be kept below 100 Ohms for all 2 state circuits. Typical 22 AWG wire has a resistance of 16.5 Ohms per 100 ft. 3. It is suggested where longer lengths than 5000 ft are required the conductor be sized at 18/2 or larger. 4. 2 state wiring is the most common but does not allow for conductor supervision. 5. 3 state hookups provide switch status as will as near complete circuit supervision. 6. 4 state hookups provide complete supervision of all states of the circuit. REV 2.0 21