Download CGP Electronics TP-42 Specifications
Transcript
Important: On FAC, FEC, VMA16, and IOM Series controllers only, the 128 DIP switch on the controller’s device address DIP switch block is a mode switch used to enable the controller to operate in a wireless mode using the ZFR1800 Series Wireless Field Bus System. On any FAC, FEC, VMA16, or IOM Series controller that is hardwired to an MS/TP Bus, set the 128 DIP switch to the OFF position. Operating any FAC, FEC, VMA16, or IOM that is hardwired to an MS/TP Bus with the controller’s 128 DIP switch set to the ON position results in communication failure on the bus. As you set the device address, the best practice is to set the highest switch value first, then the next highest switch value, and so on, until the total of the switch values equal the intended device address. For example, positioning switches 16, 4, and 1 to ON (as shown in Figure 8) sets the device address to 21 for a device on the FC bus. Figure 8: Setting the Device Address and Wireless Operation Mode on the ADDRESS DIP Switch Block Note: You must set switch 128 to OFF on all Metasys controllers that are hardwired to an FC Bus. Set switch 128 to ON only on FACs, FECs, VMA16s, and IOMs that operate on a Metasys ZFR1800 Series Wireless Field Bus. Note: Devices may go offline momentarily when a device address is changed on an active bus. A device reset is not required on field controllers or supervisory engines after changing the MS/TP address. Some devices, such as the TEC26xx Series thermostats and third-party MS/TP devices, use their own configuration settings to establish the device address for their connection to the bus. Refer to the device manufacturer’s product documentation for instructions on setting the device address. The device address values for TEC26xx thermostats and all third-party devices must comply with the rules and ranges described previously. Enabling Field Controllers for Wireless Operation The ZFR1800 Series Wireless Field Bus System enables wireless communication, allowing you to create wireless connections between NAEs or NCEs and FACs, FECs, or VMA16s. Note: The ZFR1800 Series Wireless Field Bus System is not supported on the Remote Field Bus. On FAC, FEC, and VMA16 controllers, you can enable the controller to operate with a ZFR1800 Series wireless system and connect an MS/TP Bus in a wireless mode by setting the 128 DIP switch on the device address DIP switch block to ON. See Figure 8 for more information. To operate with a ZFR1800 Series field bus, an FAC, FEC, or VMA16 must be connected to a ZFR1811 Wireless Field Bus Router, and the associated NAE or NCE must be connected to a ZFR1810 Wireless Field Bus Coordinator. See Related Documentation for references to more information about the ZFR1800 Series Wireless Field Bus System, FACs, FECs, VMA16s, NCEs, and NAEs. Local FC Bus Rules and Specifications Table 5, Table 6, and Figure 9 provide rules and specifications for the local FC bus. (For the Remote Field Bus, see Table 10.) Metasys MS/TP devices generate less data traffic than third-party MS/TP devices and TEC26xx thermostats. Connecting third-party devices or TEC26xx thermostats to the FC bus increases data traffic, reduces bus performance, and reduces the number of devices that can be connected to the FC bus. MS/TP Communications Bus Technical Bulletin 21