Download Eaton Powerware 9910 UPS User`s guide
Transcript
Specifications Model 4500 UPS (Nominal Operating Specifications) Output VA Output Voltage Output Watts Input Current Output Current Normal (BTUs/hr) On Battery (BTUs/hr) 3750 200 2500 14.6A 19.0A < 1200 < 1600 3900 208 2600 14.6A 19.0A < 1200 < 1700 4125 220 2750 14.6A 19.0A < 1300 < 1800 4300 230 2900 14.6A 19.0A < 1400 < 1900 4500 240 3000 14.6A 19.0A < 1400 < 1900 Model 4500 with PPDM (Nominal Operating Specifications) Output VA (PPU) Output Voltage (PPU) Output Watts Normal (BTUs/hr) On Battery (BTUs/hr) 3750 200 2275 < 1900 < 2400 3900 208 2375 < 2000 < 2400 4125 220 2525 < 2000 < 2500 4300 230 2675 < 2100 < 2600 4500 240 2775 < 2200 < 2700 Physical Specifications Parameter PPU Battery Cabinet PPDM Height 283 mm (11.13 in) 142.5 mm (5.61 in) 283 mm (11.13 in) Width 252 mm (9.91 in) 252 mm (9.91 in) 252 mm (9.91 in) Depth Plug/Receptacle: 406 mm (16 in) Hardwired: 463 mm (18.25 in) 400 mm (15.75 in) Plug/Receptacle: 406 mm (16 in) Hardwired: 463 mm (18.25 in) Weight 18 kg (39 lb) 23.6 kg (52 lb) 37 kg (82 lb) 70 Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.com