Download TMC-3D Multi-Axis Motion Controller
Transcript
Absolute maximum (duration ≤ 10ms) Supply current values, surge † -100 +60 V 400 mA +VLOG = 12V 350 +VLOG = 24 V 150 250 mA +VLOG = 48 V 80 150 mA Typ. Max. Units Motor Supply Input Measured between +VMOT and GND. Supply voltage Min. Nominal values, including ripple & brakinginduced over-voltage up to ±25% 12 80 VDC Absolute maximum values, continuous 0 100 VDC -0.5 105 V 1.5 mA 16.5 A 100 A Absolute maximum (duration ≤ 10ms) values, surge † Idle Supply current 0.5 Operating Absolute maximum (duration ≤ 10ms) values, surge † I/O Supply Input (isolated) Measured between +24 VPLC and 0VPLC. Nominal values Supply voltage Absolute maximum (duration ≤ 10ms) values, surge † Min. Typ. Max. 8 24 30 VDC 32 V -100 Units All inputs and outputs disconnected 20 30 mA Supply current All inputs tied to +24 VPLC; all outputs sourcing simultaneously their nominal current into external load(s) 700 1000 mA Isolation voltage rating Between 0VPLC and GND 200 VRMS Units CAN-Bus Supply Input (isolated) Measured between CAN_V+ and CAN_GND. Nominal values Supply voltage Absolute maximum (duration ≤ 10ms) Supply current Isolation voltage rating values, † surge Min. Typ. Max. 8 24 30 VDC 32 V -75 CAN-Bus idle 12 25 mA CAN-Bus operating at 1Mbit/s 60 180 mA 200 VRMS Between CAN_GND and drive GND Motor Outputs © Technosoft 2008 12 TMC3D Technical Reference