Download Carrier 38QRF036 Specifications
Transcript
40QNC018-036 Cooling Only 40QNQ018-036 Heat Pump Duct-Free Fan Coil Units Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS ...................... 1 GENERAL ........................................ l INSTALLATION ................................ 1-13 Step 1 -- Complete Pre-lnstallation Checks ...... l i UNPACK UNITS i INSPECT SHIPMENT f CONSIDER SYSTEM REQUIREMENTS Step 2 -- Mount Unit ............................. 5 Step 3 -- Complete Refrigerant Piping Connections ................................... 5 i REAR PIPING i SIDE ORBOTTOM PIPING i ROUTING THE DRAIN HOSE AND REFRIGERANT PIPING i INSTALLING THE INDOOR UNIT BODY TO THE WALL HANGING BRACKET i OUTDOOR UNITS i MAKE PIPING SWEAT CONNECTIONS i AIR PURGING AND LEAK TEST Step 4 -- Make Electrical Connections ........... 8 START-UP ....................................... 13 SERVICE ........................................ 14 TROUBLESHOOTING SAFETY .......................... 14,15 CONSIDERATIONS Before installing or servicing system, always turn offmain power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable. Electrical shock can cause serious personal injury. GENERAL This system uses R-410A, which Ms higher pressures than R-22 and other refiigerants. No other refrigerant may be used in this system. All equipment must be desiNled to handle R-410A retiigerant. If unsure about equipment, consult the equipment manufacturer. These instructions cover the installation, start-up and service of cooling only and heat pump duct-fiee systems. INSTALLATION Step 1 -- Complete Pre-lnstallation Checks UNPACK UNITS (See Fig. 1) 6 Move the unit to final location. Relnove unit fiom carton, being careful not to damage service valves and miltes. See Table 1A tbr installation materials included in shipment and see Table 1B for field-supplied materials needed to complete the installation. Installing and servicing air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install or service air-conditioning equipment. Untrained personnel can perform basic maintenance, such as cleaning and replacing filters. All other operations should be pertbnned by trained service personnel. When working on air conditioning equipment, observe safety precautions in literature, tags, and labels attached to unit. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinmlisher available. Read these instructions thom,Lghly. Consult local building codes and the National Electrical Code (NEC) for special installation requirements. Manufacturer Fig. 1 -- 40QNC,QNQ Units reserves the right to discontinue, or change at any time, specifications Catalog No. 02-40QN0001-SI Printed in U,S.A. or designs without notice and without incurring obligations. Form 40QN-SSI Pg 1 3-06 Replaces: New Table 1A -- Installation Materials -- Included In Shipment DESCRIPTION Wall Hanging QTY USAGE For indoor unit installation. Bracket Screws, 4xL10 For affixing unit and hanging bracket. 5/14" Screws, 5xL25 Wireless Remote Control Mounting Bracket For wall hanging bracket installation. For wireless remote control mounting bracket installation. For wireless remote control installation. "40QNC01824, 40QNQ018,024:5 40QNC,QNQ030,036:14 Table 1 B -- Installation Materials -- Field-Supplied NAME Connection Pipe (nominal capacity) SPECIFICATIONS Liquid line: 3/8 in. (40QNC,QNQ018-036) Mixed Phase line: 5/8 in. (40QNC01824 and 40QNQ018, 024), 3/4 in. (40QNC,QNQ030,036) Wall Sleeve Wall Cap Finishing Tape PVC Film Fastening Tape Pipe Insulation Drain Hose 5/8 in. (40QNC01824 and 40QNQ018,024) 3/4 in. (40QNC,QNQ030,036) Sealer Putty Power Supply Cable AWG 14 or higher Electrical Connecting Cable Between Indoor and Outdoor Unit Cable Type: AWG 14 synthetic rubber insulation with Neoprene coating, according to NEC codes. LEGEND AWG -NEC -- American Wire Gauge National Electrical Code INSPECT SHIPMENT 6 File a claim with the shipping company if shipment is dmnaged or incomplete. Check the unit nameplate to ensure unit matches the job requirelnents. CONSIDER SYSTEM REQUIREMENTS d Consult local building codes and NEC tbr special installation requirelnents. Use only designated indoor units with outdoor units. See Tables 2 and 3. See Fig. 2 for unit dimensions. Allow sufficient space for airflow cleaxance, wiring, reli-igerant piping, mid servicing units. See Fig. 3. Avoid mounting the unit in areas that are: Y exposed to direct sunlight f too close to heat somces f too close to humid conditions f located in an area with oily ambient conditions. Table 2 -- Matching Indoor Units to Outdoor Units OUTDOOR UNIT COOLING ONLY OR HEAT PUMP INDOOR UNIT 38HDF018 Cooling Only 40QNC01824 38HDF024 Cooling Only 38HDF030 Cooling Only 40QNC01824 40QNC030 38HDF036 Cooling Only 40QNC036 38QRFO18 Heat Pump 40QNQ018 38QRF024 Heat Pump 40QNQ024 38QRF030 Heat Pump 40QNQ030 38QRF036 Heat Pump 40QNQ036 = A A 40QNC,QNQ 018-024 DIMENSIONS (in.) 42.5 40QNC,QNQ 030, 036 DIMENSIONS (in.) 57.5 B 11.6 13.4 C 7.9 9.5 f 40QNC,QNQ Fig. 2 -- Unit Dimensions rain. 4 in. rain. ITIIR. f -- \ 80 in. rain. m 40QNC,QNQ UNITS Fig. 3 -- Unit Clearances _ ,,3 Table 3 -- Physical Data SYSTEM SIZE NOMINAL CAPACITY (Btuh) OPERATING WEIGHT (Ib) MOISTURE REMOVAL RATE (Pints/hr) (40QNC/QNQ) REFRIGERANT Type Control Device (Cooling) Control Device (Heating) Factory Charge (Ib)* INDOOR FAN Rpm/Cfm (High) Rpm/Cfm (Med) Rpm/Cfm (Low) Motor Watts Blowers Quantity...Size INDOOR COIL Face Area (sq ft) No. Rows FPI (40QNC/QNQ) Circuits FILTERS Quantity...Size AIR SWEEP Horizontal Vertical (in.) OPERATING LIMITS Heating (MiniMax) Cooling (MiniMax) CONTROLS Remote Controller Options Diagnostics Defrost Method Timer Mode Warm Start Feature Test Mode Freeze Protection Dehumidification Mode Fan Mode Auto Changeover Auto Restart Control Voltage System Voltage REFRIGERANT LINES Connection Type Mixed Phase Line (in.) OD Vapor Line (in.) OD Max Length (ft) Max Lift (Fan coil above) (ft) Max Drop (Fan coil below) (ft) CONDENSATE DRAIN Size (in.) 018 024 030 036 18,000 24,000 30,000 36,000 31 31 51 51 5.4/5.2 7.9/7.9 8.8/9.2 13.0/12.8 Accurator Accurator 6.0 I 6.3 ----- I 7.4 I 10.6 1335/645 1120/525 1000/460 64 1...4.0 x 33.7 1335/645 1120/525 1000/460 64 1...4.0 x 33.7 1030/730 930/630 830/530 74 2...4.2 x 23.5 1200/900 1050/750 900/600 74 2...4.2 x 23.5 3.0 2 16/16 5 3.0 2 16/20 5 4.9 2 18/18 9 4.9 2 18/18 9 2...12.5 x 16.11 2,..12,5 Automatic Manual I x 16.11 3..,17.3 Automatic Manual I x 16.11 3..,17.3 Automatic I x 16.1 Automatic --/81 F db 59 F wb, 70 F db/74 F wb, 90 F db Integrated Microprocessor Wireless, CRC, CZM Yes Demand Defrost Yes Yes Yes Yes Yes Yes Yes Yes 24v 208/230 Flare 3/613/613/613/6 5/8 5/8 3/4 3/4 200 60 60 5/80D, 7/16 ID I 5/80D, 7/1GID I 3/40D, 5/9 ID I 3/40D, 5/9 ID LEGEND db FPI ID wb R-410A Piston at Outdoor Unit Piston at Outdoor Unit dry bulb Fins Per Inch Internal Diameter wet bulb *Factory charge is based on 25 ft of interconnecting line. Step 2 -- Mount Unit -- Before mounting the 40QNC, QNQ unit on the wall with a walt hanging bracket, consider how the unit will be connected to the reliigerant piping. The indoor unit can be connected in four ways. Refer to Fig. 4 tbr connection options. When the piping is connected to points 1, 2 or 4, relnove the kalockout either at the side or at the bottom of the unit. The iMoor units are mounted on the walt with a wall hanging bracket. Position the wall hanging bracket so that it is tlush with the ,a_all.See Fig. 5 for service clearances. See Fig. 6 for walt bracket dimensions. 5 in. rain. i°: 7°i Plumb line Complete the tbllowing when installing the wall hanging bracket: 1. Before installing the wall hanging bracket to the wall, relnove it tioln the indoor unit by pushing at the iMicated pressure points at the bottom of the unit. 1 2. Install the walt hanging bracket in a location that is strong enough to withstand the weight of the unit. 3. Install the walt hanging bracket so that it is level. Use a plumb line if necessary. See Fig. 5. NOTE: Be sure that the wall hanging bracket is level. If the wall hanging bracket is not level, water wilt leak tiom the indoor unit. _Screw 4. Fasten the wall hanging bracket to the wall with 4 or more screw anchors thiough the holes near the outer edge of the bracket. Fig. 5 -- Installing 5. Install the wall hanging bracket tlush to the wall, and ensure the bracket does not move. 6. If the unit is relnoved tiom the wall hanging bracket after installing it on the walt, relnove it by pushing up on the indicated marks at the bottoln of the unit body. Step 3 -- Complete Refrigerant Piping Connections -- When running the piping for indoor units the piping can be connected as rear piping oi side oi bottoln piping. Refer to Fig. 4. REAR PIPING d Route the piping behind the indoor unit so that the piping is concealed by the unit. For rear piping installation, drill a 21/2in. diameter hole in the walt at point A or B in Fig. 6. Drill the hole at a slope so that the outside end is lower (1/4in. to 1/2in.) than the inside end to ensure optimal drainage. Refer to Fig. 7. Pass the pipe through the hole. SIDE OR BOTTOM PIPING d Relnove the kalockout in the unit and pass the piping through the wall. The pipe should slope downward and away ti'om the unit to ensure optimal drainage. the Wall Bracket 35.4" 2.8" 14.9" _ _5' 2.1" _' . o 40QNC01824, _ ° 40QNQ018,024 4oo,,,e.o,,,oo3o,o3o I, Fig. 6 -- Wall Bracket Dimensions ROUTING THE DRAIN HOSE AND REFRIGERANT PIPING 6 The drain hose and drain cap are assembled as shown in Fig. 8 in the factory. To do right-side (O), rightbottom ((2)) or right-back (®) piping in Fig. 4 draw the drain hose to right-side piping direction. (It is not always necessary to exchange the location of drain hose and drain cap.) 1. Tie together the reliigerant piping, the drain hose, and the electrical connection wire. v@ J @ Fig. 4 -- Indoor Unit Piping Configurations 2. Route the refrigerant piping in the required direction, and bend carefully avoiding pipe detbnnation. 3. Bind the drain hose and the electrical connection wire together with thstening tape. 4. The drain hose should be at the bottom. See Fig. 9 and 10. 5. For left-hand piping, tit the pipes and the wiring into the recess at the back of the unit. 0 Drill at Slope Outdoor [ 0 o side i \1o oo! 0 o 0 o ",...,.,,_A-"-_. ........ O_._.O_t/4o o to 1/2 in. lower _) @ Indoor unit piping @ Connection @ Drain hose Fig. 7 -- Placement of Connection wiring Piping Fig. 10 -- Location of Piping, Hose and Wiring OUTDOOR UNITS 6 Outdoor units may be connected to indoor units using field-supplied robing of retiigerant grade and condition. See Table 3 tbr correct line sizes. Do not use less than 10 ft of interconnecting robing. Fig. 8 -- Location of Drain Hose and Cap DO NOT BURY MORE THAN 36 IN. OF REFRIGERANT PIPE IN THE GROUND. If any section of pipe is buried, there must be a 6-in. vertical rise to the valve connections on the outdoor unit. If more than the recolrnnended length is buried, refiigermlt may migrate to cooler, buried section during extended periods of system shutdown. This causes reti-igerant slugging mid could possibly daanage the compressor at start-up. ® @ @ @ @ @ Fig. 9 -- Location INSTALLING THE INDOOR WALL HANGING BRACKET Indoor unit piping Left-hand piping Bind with fastening Drain hose Connection wire tape of Piping UNIT BODY TO THE 1. Pass the pipes through the walt sleeve mid then hook the indoor unit body on top of the wall hanging bracket. 2. For left-hand piping, hang the unit on top of the wall hmlging bracket and incline the unit using a toot such as a screwdriver set between the middle area of the body mid bottom right of the walt hanging bracket. Connecting the pipe can be done more easily if the unit is inclined. 3. Fix the bottom part of the unit to the walt hanging bracket by pushing it carethlty until the two bracket hooks fit into the marked places at the base of the unit until it snaps into place. Refer to Fg. 11. NOTE: f Do not crush or kink the indoor piping. Avoid sharp bends with a bend radius of less than 4 inches. f Do not over bend the sane part of the pipe lfequently. f Do not remove the flare nut fiom the indoor unit pipe until the piping is connected. NOTE: Both mb:ed phase and vapor refiigerant lines must be insulated. If either retiigerant tubing or indoor coil is exposed to the annosphere, the system must be evacuated follc_ving good reli-igeration practices. Run refiigerant tubes as directly as possible, avoiding unnecessary turns aald bends. Suspend refi-igerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to structure. Also, when passing reti'igermlt robes throu_l a wall, seal the opening so that vibration is not transmitted to structure. Leave some slack in reiiigerant robes between structure mid outdoor unit to absorb vibration. MAKE PIPING SWEAT CONNECTIONS 6 Remove plastic caps tiom liquid and suction sen:ice valves. Use refi-igerant grade tubing. Position tube end downward and cut the tube to the requested length. Remove the burrs with a reamer. See Fig. 12. NOTE: Oil in the compressor is extremely susceptible to moisture absorption. Keep ends of robing sealed during installation. Remove flare nuts tiom the unit connections and place them on the robe end. Flare the robe with the flaring tool. The flare end must not have aaly burrs or imperfections. The length of the flared walls must be uniibnn. See Fig. 13. UNIT SIZE DIMENSION Lubricate the robe end and thread of the flare fitting with antitieeze oil. Tighten the fitting several turns, then ti_lten it fully with two wrenches by applying the tightening torque indicated in Table 4 and Fig. 14. B Wall Hanging Bracket Hook 40QNC01824 10.6 40QNC030 12.2 40QN0036 12.2 40QNQ018 10.6 40QNQ024 10.6 40QNQ030 12.2 40QNQ036 12.2 Insufficient tightening torque will cause gas leaks. Overti_ltening the fittings will damage the tube tlaring and cause gas leaks. Equipment damage and personal injury may result. Hole AIR PURGING AND LEAK TEST d Only use a vacuum pump to puNe air fiom the piping. Refer to Fig. 15. Retainer Retainer o\f ? I IMPORTANT: Do not use the system compressor as a [ vacuulrl I pulrlp. I IMPORTANT: Do not use the unit refiigerant gas to purge [ the connecting pipes. I Fig. 11 -- Wall Hanging Details Relnove the caps fioln the valves. Create a vacuum with a vacuuln pump connected to the selwice connection of the suction shut-off (gas), as shown, keeping the shutoff valves colnpletely shut until a 50 Pa vacuum has been reached. Open the mixed phase valve for 3 seconds, then quickly shut it to check for possible leaks. Replace caps and check for leaks using a leak detector specific for R-410A refi-igerant. After the leak test, fully open the tbaee-way valves. Table 4 -- Tightening Torque VALVE SIZE Fig. 12 -- Removing Burrs FLARE NUT (in.-Ib) 3/8 in. 372 5/8 in. 487 3/4 in. 885 I ® @ Adjustable wrench or torque wrench @ Outdoor end @ Indoor end Fig. 14 -- Tightening Connections Fig. 13 -- Flared Walls are Equal ® @ Three-way @ Flare nut @ Liquid @ Valve cap @ Mixed-phase @ Valve needle @ Indoor unit @ Needle valve (mixed-phase) valve line (small @ Allen (hex. head) wrench @ Outdoor unit @ Two-way @ Vacuum pump valve (liquid) diameter) line (large diameter) Fig. 15 -- Air Purging Step 4 -- Make Electrical Connections Unit cabinet must have an uninterrupted, unbroken electrical mound to minilnize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical mound when installed in accordance with NEC, and local electrical codes. Failure to tbtlow this warning could result in the installer being liable for the personal injury of others. Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty. Before performing seiwice or maintenance, be sure main power switch is turned OFF and indoor blower and outdoor tan have stopped. Failure to do so may result in electrical shock or injury tiom rotating tan blades. POWER WIRING (Fig. 16-19) d Unit is thctory wired for voltage shown on nmneptate. Provide adequate, fused disconnect switch within sight of unit, readily accessible, but out of rea& of children. Provision tbr locking the switch open (oil) is advisable to prevent power fiom being turned on while unit is being seaTiced. Disconnect switch, fuses, and field wiring must comply with the NEC and local code requirelnents. Use copper wire only between the disconnect switch and unit. Use minimum 60 C wire for the field power connection. Open the fan coil control box panel and connect the indoor and outdoor units. Connect the wires through the terminals as shown on the unit label diagam and in Fig. 16-19 and Table 5. Unit must be grouMed. THERMISTOR EQUIVALENCE TEMPERATURE STEP I.R. I I _ |i _._ z MOTOR °C o 85 35 B, 500 72 22 11,400 32 0 32,500 DRIVE REMOTE _ DISPLAY I I _ RES ] STANCE °F ALL THERMISTORS ARE IDENTICAL 2 il 23 so7 I I 0 YEL YEL LED BOARD ]R l' CON i °Yo N JlO 24V COMPR TB3 _]X, MODULAR 1PCB _A _ CONTROL _GRN/YEL TO LEGEND EQUIP. TERMINAL 0 _ D[5CONNECT [MARKED) TERMINAL TERMINAL PLICE UNIT GND [UNMARKED) BLOCK FACTORY WIRING FIELD CONTROL FIELD POWER ACCESSORY OPTIONAL WIRING WIRING OR WIRING IPCB MAIN CONTROL CIRCUIT BOARD STM LOUVER STEPPER TP TEST TRAN TRANSFORMER PRINTED MOTOR 400NC 01824 POINT HIGHWALL 38HDF OUTDOOR CONDENSER BLK _2_ _ _ YEL BLK UNIT DISCONNECT OUTDOOR I i _ BLK E_ E_ _ OFR ED BLU W/PNK _ TO HIGHWALL Y TO HIGHWALL R TRAN TB__2L Fig. 16 -- 40QNC01824 Matched with 38HDF Typical Wiring Schematic Jl J THERMISTOR J EQUIVALENCE TEMPERATURE STEP I.R. MOTOR DRIVE REMOTE _ DISPLAY " # / 4567 2 RES [STANCE °F °C 95 35 72 22 32 0 ALL u 5,500 11,400 32, THERMISTORS ARE SO0 IDENTICAL E ,,I_ Im I YEL BY l i INTERNAL THERMAL OVERLOADS. D 4. TRANSFORMER THE PRIMARY 5. COMPRESSOR CRANCKCASE ON 538QNF030. YEL LED BOARD [R COM HAS £1DE INTERNAL 2A HEATER THERMAL FUSE INSTALLEO JlO z I TBB MODULAR _A_ CONTROL IPCB CONTACTOR CAP CAPACITOR CH CRANKCASE COMP COMPRESSOR CHS OFT CRANKCASE DEFROST FC FAN HEATER _GRN/YEL_ HEATER THERMOSTAT SWITCH EQUIPMENT HIGH IDFM INDOOR LLPS LIQUID OAS OFM OUTDOOR OUTDOOR AIR FAN SENSOR MOTOR OFR OUTDOOR FAN RELAY OL OVERLOAD IPCB PRESSURE GROUND HPS FAN PRESSURE MAIN CONTROL PRINTED CIRCUIT RVS REVERSING 5TM LOUVER TP TEST TRAN TRANSFORMER 1 EQUIP, GND SWITCH MOTOR LOW 5432 LEGEND CAPACITOR EQUIPGND. VALVE STEPPER SWITCH 0 TERMINAL (MARKED) TERMINAL (UNMARKEO) SPLICE TERMINAL BLOCK FACTORY BOARD SDLENOIO WIR[NG FIELD CONTROL FIELD POWER _ WIRING m m_ WIRING MOTOR ACCESSORY OPTIONAL POINT OR WIRING 400N8018 024 NIGNWALL 38QRF OUTDOOR CONDENSER I ........ YEL _ __ -L OH I.OTE s CHSyI OUTDOOR _I, _I _ L vCOMP BLK BRN_ RED _ AP GR UNIT DISCONNECT TO m _ _ BLK _ TO TO HIGHWALL HIGHWALL A B TO HIGHWALL DT TO HIGHWALL G TO HIGHWALL Y TO HIGHWALL R TO HIGHWALL 0 OFR O_FTOBLK BLU W/PNK _ _ J J RVS{_]V_]V_]V_sBLK TRAN _ TB_ Fig. 17 -- 40QNQ018,024 Matched with 38QRF Typical Wiring Schematic 10 ON o_ CN <0 FqZ THERMI5TOR EQUIVALENCE TEMPERATURE RESISTANCE °F °C 95 35 8,500 Q 72 22 11,400 32 0 32,500 ALL THERMISTORSARE IDENTICAL NOTES 1. ..... I_ IF IDc RA I _ ANY MUST WITH 4. DISPLAY INVERTER THE ORIGINAL BE REPLACED, IT TYPE 90_C WIRE WIRE FURNISHED MUST BE REPLACED OR ITS EQUIVALENT. _ _T_%**_%_"_ _!_?_g°Sc _........ _._?"_O_L_%;_2L_OSOt_O;?L ......... RED I0 OF TRANHBFORMIEMRAR_ABs I NT _ ................. REMOTE BLK B ORN 2 CRY COMPR BLN TB3 MODULAR "D _ CONTROL 1PCB J_ -- BLU_ o< cz o BOARD I/O r INDOOR J2o 1 I FAN J7 I 7654321 EQUIP. BLK C CONTACTOR CAP CAPACITOR COMP FC COMPRESSOR FAN CAPACITOR EQUIP.GNO. BLU < RED EQUIPMENT HPS HIGH PRESSURE IDFM INOOOR FAN LLP5 OFM LIQUIO OUTDOOR OFR OUTDOOR OL OVERLOAD IPCB MA[N BTM PRINTED LOUVER TP TRAN TEST POINT TRANSFORMER GROUND SWITCH (_} TERMINAL LEGEND 0 TERMINAL MOTOR LOW PREBBURE FAN MOTOR FAN 5W[TCM • RELAY D ..... BOARD MOTOR (MARKED] (UNMARKED) SPLICE TERMINAL FACTORY CONTROL CIRCUIT STEPPER GND < _ BLOCK WIRING FIELD CONTROL FIELD POWER FC WIRING WIRING 400NC030 038 HIGHWALL 38HDF OUTDOOR CONDENSER EOUIP GNO_ _ _ 208/230V 1PH BLK YEL 0RN :: _1 _111 __-oufgooR DISCONNEcTUNIT BLK m BAP E_ _BLK OFR E_ BLU W/PNK _ TO HIGHWALL Y TO HIGHWALL R E_ TRAN TB=__L Fig. 18- 40QN0030,036 Matched with 38HDF Typical Wiring Schematic 11 Jl J o= THERMISTOR CN <:0 FqZ ©rqq RES [ STANCE °F °C o 95 35 6,500 72 32 22 0 ALL _ EQUIVALENCE TEMPERATURE 11 , 400 32,500 THERMISTORS ARE IDENTICAL _ L I I i I_ [DC AY 5 • BY INTERNAL THERMAL OVERLOADS• RA DISPLAY INVERTER 4, TRANSFORMERHAS INTERNAL 2A THERMAL FUSE ON THE PRIMARY SIDE, 5, COMPRESSORCRANCKCASE HEATER INSTALLED ON 538QNF030. REMOTE BLK OAS _WHT OUTOR OO FAN DEFROST _OAS 3 2 ORN GRY BLK COMPR 24V I TB3 _[_]_ CONTACTOR CAP CAPACITOR CH CRANKCASEHEATER COMP COMPRESSOR CHS CRANKCASEHEATER SWITCH OFT DEFROST THERMOSTAT FC FAN CAPACITOR EQUIP,GND, EQUIPMENT GROUND HPS HIOH PRESSURE SWITCH IDFM INDOOR FAN MOTOR LLPS LIQUID LOW PRESSURESWITCH OA£ OUTDOORAIR BENSOR OFM OUTOOORFAN MOTOR OFR OUTOOORFAN RELAY OL OVERLOAD 1PCB MAIN CONTROL PRINTED CIRCUIT BOARD RVS REVERSIN8 VALVE SOLENOID STM LOUVER STEPPER MOTOR TP TEST POINT TRAN TRANSFORMER MODULAR CONTROL _D _ 1PCB BLU_ E I/O F BOARD J20 iNDOOR ]1 J7 FAN 1 7654321 EQUIP. BLK o TERMINAL TERMINAL BLU (MARKED] (UNMARKED) @ SPLICE __LEGEND__ TERMINAL BLOCK FACTORY WIR]NG FIELD ..... GND < RED =__m m_ OONTROL WIRING FIELD POWER WIRING ACCESSORY OR FC 40QNQ030 038 HIGHWALL .............. 38QRF OUTDOOR CONDENSER 5 LI UNIT - DISCONNECT OUtdOOR BRN_ AP 6R TO HIGHWALL B TO HIGHWALL A TO HIGHWALL OT TO HIGHWALL G TO TO HIGHWALL HIGHWALL Y R TO HIGHWALL O OFR OFT BLU W/PNK Rvs[_s TRAN BLK _] _ TB._.21 Fig. 19 -- 40QNQ030,036 Matched with 38QRF Typical Wiring Schematic ]2 _I Table 5 -- 40QNC,QNQ Fan Coil Electrical Data VOLTAGE RANGE* UNIT SIZE V-PH-Hz Min Max FLA FAN Motor Power (Watts) 64 74 POWER MIN WIRE SIZE MCA MOCP 0.48 0.48 15 15 14 14 40QNC01824 40QNC030 208/230-1-60 208/230-1-60 187 187 253 253 0.38 0.38 40QNC036 208/230-1-60 187 253 0.44 74 0.55 15 14 40QNQ018 208/230-1-60 187 253 0.38 64 0.48 15 14 40QNQ024 208/230-1-60 187 253 0.38 64 0.48 15 14 40ONO030 40QNQ036 208/230-1-60 208/230-1-60 187 187 253 253 0.38 0.44 74 74 0.48 0.55 15 14 14 LEGEND FLA MOA MOCP NEC RLA ------ NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or equipped with a breaker. 2. Motor RLA values are established in accordance with UL (Underwriters Laboratories) Standard 465. Full Load Amps Minimum Circuit Amps per NEC Section 430-24 Maximum Overcurrent Protection National Electrical Code Rated Load Amps (Compressor) *Permissible limits of the voltage satisfactorily. range at which 15 unit will operate START-UP Configuring Two Indoor Unit Remote Controis -- It"two indoor units are being installed in the same room, working independently, two relnote controls need to be configured for proper operation. UNIT CONFIGURATION 6 Turn the unit off by pressing Preliminary Checks 1. Check that all internal wiring connections are tight and that all ban-iers, covers, and panels are in place. 2. Field electrical power source must a mee with unit nameplate rating. 3. All service vanes must be open. 4. Crankcase heater must be tight on compressor crmlkcase (if equipped). the _. Press and hold the N_ and _ buttons of the remote control for more than 5 seconds. The display will be cleared and the time semnents wilt display the first confimlration item (rAdr relnote address) and the temperature semnents will display the default value of this configuration item Leak Test -- Field piping and tan coil must be leak tested by pressure metllod. Use R-410A at approxilnately 25 psig backed up with an inert gas to a total pressure not to exceed 245 psig. NOTE: Leak detectors should be desiNled to detect HFC (hydrottuorocarbon) refrigerant. (Ab control of both indoor units). Press _ and V to change the default value to the new value of(a) or (b). Press the Evacuate and Dehydrate -- Field piping and fan coil must be evacuated and dehydrated t\_ltowing good retiigeration practices. off by pressing the (1) Start Unit with Operating Test -- L_ button to transmit the new configuration to the unit. Press the (!) button to leave the configuration menu. REMOTE CONTROL CONFIGURATION 6 Turn the unit and (Ab control of both indoor units). Press A and V to &ange the default value to the new value of(a) or (b). Press the the _ buttons on the relnote control tbr 5 seconds. The relnote control will be cleared and the time semnent wilt display the Src 1 service test mode. _ button to transmit the new confi_ration to the unit. Press the 0!) button to leave the configuration menu. Press the =_ button to translnit the service test siNml to the unit. After the test has completed press the (!) the test menu. and _ buttons for more than 5 seconds. The display will be cleared and the time segnnents will display the first configuration item (CH relnote address) and the temperature semnents wilt display the default value of this configuration item Turn power on to the unit. Insert batteries in relnote control. Press the A button. Press aald hold the V NOTE: When 30 seconds have elapsed and no buttons have been pressed, the remote control will automatically exit the configuration menu and res_ulneits norlnal operation. button to leave NOTE: When 30 secoMs have elapsed and no buttons have been pressed, the relnote control will automatically exit the test menu and resume its norlnal operation. 13 NOTE: Do not install a suction-line filter drier in the mixed phase line. SERVICE Refrigerant Betbre pertbnning recomlnended maintenance, be sure unit main power switch is turned off Failure to do so may result in electrical shock or injury tbnn rotating fan blade. Charging To prevent personal injury, wear safety glasses and gloves when handling reti-igerant. Do not overcharge system d this can cause compressor flooding. Pu mpdown Procedure -- The system may be pmnped down in order to make repairs on the low side without losing complete retiigerant charge. 1. Attach pressure gage to suction service valve gage port. 2. Frontseat the mixed phase line valve. NOTE: Do not vent or depressurize unit retiigerant to atmosphere. Relnove and recover refiigerant following accepted practices. TROUBLESHOOTING See Tables 6 and 7 for troubleshooting intbnnation. The unit coils hold only the factory-desiNlated amount of refrigerant. Additional refrigerant may cause units to relieve pressure tbaough the compressor internal pressure relief valve (indicated by a sudden rise of suction pressure) before suction pressure reaches 20 psig. If this occurs, shut off unit immediately then fiontseat the suction valve and remove and recover excess retiigerant fotbwing accepted practices. Equipment damage may result. Fault Code -- Once a failure occurs with the indoor unit in operation, the green LED on the indoor unit flashes at intervals of 0.5 seconds. The fauh code is deduced fioln the number of times the _een LED flashes, blocking unit operation. Between one flash cycle and the next one, a pause of 3 secoMs elapses. Table 6 -- Green LED (Indoor Unit Fault) 3. Start unit and run until suction pressure reaches 5 psig. 4. Shut unit offand fiontseat suction valve. CODE 5. Depressurize low side of unit and recover retiigerant following accepted practices. Filter Drier -- Whenever the filter drier is exposed to the atruosphere it must be replaced. Only use factory specified liquidline filter driers with rated working pressure of at least 600 psig or 1Ylore. 14 DESCRIPTION 3 Room Air Sensor Fault 4 14 Indoor Unit Coil Sensor Fault Outdoor Unit Air Sensor Fault Table 7 -- Troubleshooting PROBLEM POSSIBLE CAUSE Compressor and Fan of the Outdoor Unit Will Not Start SOLUTION Unit not energized Main switch is set to OFF Check the main power connection. Check and put it to ON position. Main switch fuses are blown Compressor cycling protection Replace fuses. Wait for 3 minutes. is on Main power voltage is too low Electrical connections are too loose or are wrong Check and set to the correct voltage. Compressor Will Not Start, But Outdoor Fan is Operating Electrical connections or wrong Check and tighten or repair compressor. Compressor Stops Due to Overtemperature Compressor device on of compressor are loose burnt out; seized or protection Check and tighten or correct connections. Check for the cause and replace compressor necessary. Wrong refrigerant charge in unit (excessive or low) or air or other noncondensable gasses in the circuit Drain refrigerant, Main voltage is too high or too low Condenser coil obstructed Check voltage setting and adjust if necessary. Remove obstruction. Outdoor fan off Check cause and resume operation or repair. Wrong indoor unit thermistors Replace thermistors. Check and remove obstructions. Refrigerant circuit clogged if evacuate and recharge. CAUTION: Do not vent refrigerant to the atmosphere; use refrigerant recovery equipment. Reversing valve faulty on heat pump models Replace reversing valve. Expansion device clogged or covered with ice Drain refrigerant, evacuate and recharge. CAUTION: Do not vent refrigerant to the atmosphere; use refrigerant recovery equipment. Compressor Runs Continuously Unit selected is too small for application requirements Contact a qualified service technician for a system evaluation. Indoor temperature Check temperature setting too low or too high Outdoor unit fan faulty Air or other noncondensable circuit Obstructions filters Frequent Ice-Build-Up Coil Discharge Pressure on Outdoor Too High setting. Replace outdoor fan. gasses in the at air intake or dirty indoor unit Drain refrigerant, evacuate and recharge. CAUTION: Do not vent refrigerant to the atmosphere; use refrigerant recovery equipment. Remove obstruction and/or clean filter. Outdoor fan is stopped Check cause and repair. Outdoor coil dirty or obstructed Clean or remove obstructions. Condenser fan faulty Replace condenser fan. Indoor temperature Check temperature setting. setting too low or too high Air or other noncondensable circuit gasses in the Drain refrigerant, evacuate and recharge. CAUTION: Do not vent refrigerant to the atmosphere; use refrigerant recovery equipment. Discharge Suction Pressure Too Low Pressure Too High Suction Pressure Too Low Outdoor Fan Cycling Due to Over-Temperature Protection Indoor temperature Outdoor coil dirty or obstructed setting too high or too low Check temperature setting. Clean or remove obstructions. Indoor unit air filter dirty Clean filter. Indoor temperature Check temperature setting too high or too low setting. Reversing valve faulty or internal leak Replace reversing valve. Indoor temperature Check temperature setting too high or too low setting. Evaporator coil covered with ice Air circulation on the evaporator and repair. Expansion device or suction line clogged Check and repair. Outdoor fan does not stop during defrost _eriods Check electrical parts. Electrical connection Check connections. loose Fan motor burn out Replace. Fan bearing seized Check and repair. Expansion device clogged or covered with ice Drain refrigerant, not sufficient; check evacuate and replace. CAUTION: Do not vent refrigerant to the atmosphere; use refrigerant recovery equipment. ]5 Copyright 2006 Carrier Corporation Manufacturer reserves the right to discontinue, Catalog No. 02-40QN0001-SI or change at any time, specifications Printed in U.S.A. or designs without notice and without incurring obligations. Form 40QN-8SI Pg 16 3-06 Replaces: New