Download ADAM 4000 - Cole

Transcript
Command Set
ADAM-4016 Command Table
Command Syntax
%AANNTTCCFF
Command Name
Configuration
#AA
Read Analog Input
$AA0
Span Calibration
$AA1
Offset Calibration
$AA2
Configuration Status
#**
Synchronized
Sampling
$AA4
Read Synchronized
Data
$AAF
Read Firmware
Version
$AAM
Read Module Name
4-12 ADAM 4000 Series User’s Manual
Command Description
Set the address, input range, baud
rate, data format, checksum status
and/or integration time for the
specified analog input module
Return the input value from the
specified analog input module in
the currently configured data
format
Calibrate an analog input module
to correct for gain errors
Calibrate an analog input module
to correct for offset errors
Return the configuration
parameters for the specified
analog input module
Orders all analog input modules to
sample their input values and store
them in special registers
Returns the value that was stored
in the specified module's register
after the #** command
Return the firmware version code
from the specified analog input
module
Return the module name from the
specified analog input module
Page No.
4-47
4-55
4-60
4-61
4-51
4-62
4-63
4-53
4-54