Download Liebert PEX User Manual - Large Frame
Transcript
Piping Table 13 Recommended refrigerant line sizes - OD copper mm (inches) 1020 Model Equiv. Length Gas 1025 Liquid Gas 1030 Liquid Gas 1035 Liquid Gas 2045 Liquid Gas 2055 Liquid Gas Liquid 15m (50ft) 22 13 22 16 28 16 28 16 28 16 28 16 30m (100ft) 22 16 22 16 28 16 28 19 28 22 28 22 45m (150ft) 22 16 28 16 28 22 28 22 35 22 35 22 60m (200ft) 28 16 28 19 28 22 28 22 35 22 35 22 2040 Model Equiv. Length Gas 2050 Liquid Gas 2060 Liquid Gas 2070 Liquid Gas Liquid 15m (50ft) 22 13 22 16 22 16 22 16 30m (100ft) 22 16 22 16 22 16 22 19 45m (150ft) 22 16 28 16 28 19 28 22 60m (200ft) 28 16 28 19 28 22 28 22 3080 Model 3090 3100 Equiv. Length Gas Liquid Gas Liquid Gas Liquid 15m (50ft) 28 16 28 16 28 16 30m (100ft) 28 22 28 22 28 22 45m (150ft) 28 22 35 22 35 22 60m (200ft) 35 22 35 22 35 22 Table 14 Air Cooled Model Refrigerant Charge per Circuit, kg (lb) 1020, 1025, 1030 2.3 (5.1) 1035 3.1 (6.8) 2045, 2055 4.9 (10.8) 2040, 2050, 2060 2.4 (5.3) 2070 3.2 (7.0) 3080, 3090 3.7 (8.1) 3100 5.0 (11.0) 1020 2.5 (5.5) 1025, 1030, 1035 2.75 (6.1) 2045, 2055 4.0 (8.8) 2040 2.5 (5.5) 2050, 2060 2.75 (6.1) 2070 4 (8.8) 3080, 3090, 3100 4 (8.8) Water Cooled O.D. 13 16 19 22 in. 1/2 5/8 3/4 7/8 1-1/8 1-3/8 28 Indoor unit approximate refrigerant charge for R-22 or R-407C System Type Table 15 Metric/Imperial Equivalents mm Liquid Line charges - refrigerant per 30m (100 ft) of Type “L” copper tube Liquid Line, kg (lb) 1/2" 3.3 (7.3) 5/8" 5.3 (11.7) 3/4" 7.8 (17.2) 7/8" 11.1 (24.4) 1-1/8" 18.9 (41.6) 40 35