Download EMHEATER - In
Transcript
EM11 User’s Manual 5. Description of Function Codes Diagram 5-28 Simple PLC when used as frequency source Parameter Name Setting Range Default Unit's digit: Record of power failure. 0: no record after power off Simple PLC record 1: record after power off C2-01 00 selection Ten's digit: Record of stopping. 0: no record after stopping 1:record after stopping PLC record of power failure indicates that the frequency inverter memorizes the PLC running stage and running frequency before power failure, and frequency inverter will continue to run from the memorized stage after it is powered on again. If the unit's digit is set to 0, the frequency inverter restarts the PLC process after it is powered on again. PLC record of stopping indicates that the frequency inverter records the PLC running stage and running frequency of stop, and frequency inverter will continue to run from the recorded stage after power on again. If the ten's digit is set to 0, the frequency inverter will restarts the PLC process after it power on again. Code Code C2-02 C2-03 C2-04 C2-05 C2-06 C2-07 Parameter Name Running time of simple PLC Segment 0 Acceleration/deceleration time of simple PLC Segment 0 Running time of simple PLC Segment 1 Acceleration/deceleration time of simple PLC Segment 1 Running time of simple PLC Segment 2 Acceleration/deceleration time of simple PLC Segment 2 Setting Range 0.0s(h)~6553.5s(h) 0~3 0.0s(h)~6553.5s(h) 0~3 0.0s(h)~6553.5s(h) 0~3 Default 0.0s (h) 0 0.0s (h) 0 0.0s (h) 0 97