Download GVX9000 AF Drives
Transcript
Group 50 — AC Drive Control 50.58 PID Setpoint Range: Default: 0 Source 00 Disable 01 Keypad (store in 50.66) 02 AI1 (external 0 – 10V) 03 AI2 (external 4 – 20 mA) 04 AI3 (external -10 – 10V) 05 PID set point (50.66) This parameter determines the location of PID setpoint. 50.59 PID Feedback Range: Default: 0 Source and Type 00 Positive AI1 (0 – 10V) 01 Negative AI1 (0 – 10V) 02 Positive AI2 (4 – 20 mA) 03 Negative AI2 (4 – 20 mA) 04 Positive AI3 (-10 – 10V) This parameter determines the analog PID feedback source and type. 50.60 PID P Gain Range: 0.0 to 10.0 Adjustment Default: 1.0 50.61 PID I Gain Range: 0.00 to 100.0 sec. Default: 1.00 Adjustment When this parameter is set to 0.0, this function is disabled. 50.63 PID Upper Limit Range: 00 to 100% for Integral Control Descriptions of Parameter Settings 50.62 Default: 0.00 PID D Gain Range: 0.00 to 1.0 sec. Adjustment When this parameter is set to 0.0, the function is disabled. Default: 100 50.64 PID Output Delay Range: 0.0 to 2.5 sec. Default: 0.0 Filter Time This parameter generates a delay before the PID will respond to a change. GVX9000 User Manual 5-45