Download IEC 61850 communication
Transcript
IEC 61850 communication ECI850 Sepam server Diagnostics pages PE80620 ECI850 Summary Procedure Action Result 1. From the Diagnostics page, click Opens the ECI850 Summary page. ECI850 Summary. 2. View the data See “Interpreting information” below. Interpreting information Information Description Device Information ECI850 Summary page. Firmware Version The firmware version that is installed on the ECI850 System Idle Time MAC Address A percentage from 0% to 100% indicating the average processor time that is not being used The unique Ethernet hardware address of the ECI850 Serial Number The serial number of the ECI850 Model Number The ECI850 model number Hardware Version The ECI850 hardware version Manufacture Date The date the ECI850 was manufactured IEC 61850 Device Name The name given to the ECI850 device in the IEC 61850 configuration file IEC 61850 Configuration files File Name "Current" is the last loaded CID file "Backup" is the archived CID file Name of the file as defined at loading Edit time Time at which the configuration file has been created Version Version of the file as defined in the file header Revision Revision of the file as defined in the file header Restore This button overwrites the content of the current file with the content of the backup file. IEC 61850 Logical devices Name Name of the logical device built from the configuration file Label Label of the device (Sepam label or ECI850 system name) Type of the device as declared in the configuration file Type Address Status Modbus address of the device as declared in the configuration file b Offline: the declared device does not respond to ECI850 requests b Wrong type: the device at this address is not of the expected type b Init: the device database is being initialized b Online: the device is operational b Bad Conf.: there is an error in the configuration file, the device is ignored Date and time 16 Last Successful Time Synchronization (UTC) ECI850 Date and Time (UTC) Displays the last time the ECI850 successfully contacted the SNTP server (UTC time). Current time and date of the ECI850 (UTC time). ECI850 Date and Time (local) Current time and date of the ECI850 (local time). SEPED306024EN - 10/2009