Download IEC 61850 communication

Transcript
IEC 61850
communication
ECI850 Sepam server
Diagnostics pages
PE80620
ECI850 Summary
Procedure
Action
Result
1. From the Diagnostics page, click Opens the ECI850 Summary page.
ECI850 Summary.
2. View the data
See “Interpreting information” below.
Interpreting information
Information
Description
Device Information
ECI850 Summary page.
Firmware Version
The firmware version that is installed on the ECI850
System Idle Time
MAC Address
A percentage from 0% to 100% indicating the average
processor time that is not being used
The unique Ethernet hardware address of the ECI850
Serial Number
The serial number of the ECI850
Model Number
The ECI850 model number
Hardware Version
The ECI850 hardware version
Manufacture Date
The date the ECI850 was manufactured
IEC 61850 Device Name
The name given to the ECI850 device in the IEC 61850
configuration file
IEC 61850 Configuration files
File
Name
"Current" is the last loaded CID file
"Backup" is the archived CID file
Name of the file as defined at loading
Edit time
Time at which the configuration file has been created
Version
Version of the file as defined in the file header
Revision
Revision of the file as defined in the file header
Restore
This button overwrites the content of the current file with
the content of the backup file.
IEC 61850 Logical devices
Name
Name of the logical device built from the configuration file
Label
Label of the device (Sepam label or ECI850 system
name)
Type of the device as declared in the configuration file
Type
Address
Status
Modbus address of the device as declared in the
configuration file
b Offline: the declared device does not respond to
ECI850 requests
b Wrong type: the device at this address is not of the
expected type
b Init: the device database is being initialized
b Online: the device is operational
b Bad Conf.: there is an error in the configuration file, the
device is ignored
Date and time
16
Last Successful Time
Synchronization (UTC)
ECI850 Date and Time (UTC)
Displays the last time the ECI850 successfully contacted
the SNTP server (UTC time).
Current time and date of the ECI850 (UTC time).
ECI850 Date and Time (local)
Current time and date of the ECI850 (local time).
SEPED306024EN - 10/2009