Download temporary access catwalk - SPX Cooling Technologies

Transcript
U S E R M A N UA L
temporary access catwalk
I N S TA L L AT I O N - M A I N T E N A N C E
M2013-1402
I SSU E D 06/2013
R EAD AN D U N D E R STAN D TH I S MAN UAL PR IOR TO OPE RATI NG OR S E RVICI NG TH I S PROD UCT.
catwalk components
Fan Not Shown
Temporary Access
Catwalk
Guardrail To Cover
Fan Cylinder Opening
See Caution Sign Prior To
Removing Cylinder Segment
2
catwalk installation
Warning
Always shut off electrical power to the tower fan motor prior to performing
any inspections that may involve physical contact with the mechanical or
electrical equipment in or on the tower. Lock out and tag out any electrical switches to prevent others from turning the power back on. Service
personnel must wear proper personal protective clothing and equipment.
Locking out electrical devices will not prevent the fan from spinning freely.
Secure the fan before working inside the fan area.
Review all site and owner safety manuals and follow the most stringent
requirements.
Follow all appropriate owner safety and lock-out procedures before removing a fan cylinder access segment or using the mechanical equipment
temporary access catwalk.
Do not attempt use if there is a potential for lightning storms or inclement weather.
Safety requirements for personal tie-off or fall protection shall be followed
at all times.
1—Remove and store the fan cylinder access segment and protect the opening per OSHA and owner safety requirements. Collect all loose hardware
that was removed and inspect before reuse.
2–Inspect the temporary access catwalk for damage or other defects that
could impact the safe load posted on the catwalk section. Verify all hardware, brackets, beams, guardrail, etc. are on hand for a complete and safe
installation.
3–Visually inspect the permanently installed guide track in each fan cell opening for damage and/or missing brackets or hardware.
4–Damaged parts should be repaired by qualified personnel or replaced prior
to use.
5–Keep loads below the capacity limits posted on the catwalk.
6–Handling the catwalk may require more than one person. Maneuver the access catwalk into the removed fan cylinder segment opening using the guide
track assembly which is permanently installed at each fan cell. The guide
track may be at the fan deck level or raised slightly to clear steel support
beams depending upon tower size and design.
7–Catwalk must slide under the retaining bar at the end of the guide rack.
last page
➠
3
guardrail installation – vertical rib fan cylinder
11/2" Diameter
Aluminum Guardrail
C
L Fan Cylinder Opening
C
L Catwalk
A
Fan Cylinder
3/8"
x 31/2" Bolt
Lock Washer
3/8" Nut
3/8"
Fan Cylinder
Detail
3/8"
x 11/2" Bolt
Washer
3/8" Nut
3/8"
A
3/8"
x 11/2" Bolt
3/8" Washer
3/8" Nut
6" Fiberglass Toeboard
ELEVATION VIEW
C
L Fan Cylinder Opening
C
L Catwalk
11/2" Diameter
Aluminum Guardrail
3/8"
Mechanical Equipment
Catwalk
Washer
Nut
3/8"
Aluminum
Guardrail
Detail
Fan Cylinder
6" Fiberglass Toeboard
Fan Deck
Area of Removable
Fan Cylinder Segment
4
PLAN VIEW
guardrail installation – vertical rib fan cylinder
Fan Cylinder
11/2" Diameter
Aluminum Guardrail
3/8"
x 31/2" Bolt
Lock Washer
3/8" Nut
3/8"
20°
3/8"
x 11/2" Bolt
Washer
3/8" Nut
3/8"
Fan Deck
6" Fiberglass Toeboard
6" Fiberglass Toeboard
VIEW A
3/8"
Equipment
Washer
Nut
13/8" x 51/4"
Flat Bar
3/8"
3/8"
U Bolt
Aluminum
Guardrail
2"
Fan Cylinder
DETAIL
Plain View
6" Fiberglass Toeboard
Caution
Overtightening the hardware could result in damage to the fan cylinder
and the guardrail.
5
guardrail installation – horizontal rib fan cylinder
11/2" Diameter
Aluminum Guardrail
A
C
L Fan Cylinder Opening
C
L Catwalk
Fan Cylinder
3/8"
x 31/2" Bolt
Lock Washer
3/8" Nut
3/8"
Detail
3/8"
x 11/2" Bolt
Washer
3/8" Nut
3/8"
A
3/8"
x 11/2" Bolt
3/8" Washer
3/8" Nut
6" Fiberglass Toeboard
ELEVATION VIEW
C
L Fan Cylinder Opening
C
L Catwalk
11/2" Diameter
Aluminum Guardrail
3/8"
Mechanical Equipment
Catwalk
W
3/8
Alum
Gua
Detail
Fan Cylinder
6" Fiberglass Toeboard
Fan Deck
Area of Removable
Fan Cylinder Segment
PLAN VIEW
6
guardrail installation – horizontal rib fan cylinder
Fan Cylinder
11/2" Diameter
Aluminum Guardrail
3/8"
x 31/2" Bolt
Lock Washer
3/8" Nut
3/8"
3/8"
x 11/2" Bolt
Washer
3/8" Nut
20°
3/8"
Fan Deck
6" Fiberglass Toeboard
Fiberglass Toeboard
VIEW A
3/8"
quipment
Washer
Nut
13/8" x 51/4"
Flat Bar
3/8"
3/8"
U Bolt
Aluminum
Guardrail
2"
Fan Cylinder
DETAIL
Plain View
6" Fiberglass Toeboard
Caution
Overtightening the hardware could result in damage to the fan cylinder
and the guardrail.
7
temporary access
catwalk
8–On raised installations, a temporary catwalk support beam is supplied to
support the end of the temporary catwalk on the fan deck.
9–Once the catwalk is in position under the retaining bar, install the fan cylinder
guardrail on each side of the catwalk. Refer to illustrations within this manual.
Warning
The guardrail is designed to laterally brace the catwalk. Do not use the
catwalk without the guardrail installed.
10–When fan area maintenance is complete, the instructions are reversed.
Remove temporary access catwalk and then the fan cylinder guardrail
from the fan cell. The catwalk, guardrail, support beam and any attaching hardware should be stored and secured on the fan deck in the area
designated by the owner or in storage restraints if provided.
Caution
The temporary access catwalk may be slippery. Watch your step.
Warning
The owner shall provide guarded openings and follow all OSHA and site
safety regulations if the openings are not immediately closed by reinstalling the fan cylinder access panels.
Caution
The temporary access catwalk must be removed from the fan opening
prior to starting the fan.
S PX C O O L I N G T E C H N O LO G I E S , I N C .
7401 W 129 STREET
OVERLAND PARK, KANSAS 66213 USA
P: 913 664 7400
F: 913 664 7439
[email protected]
In the interest of technological progress, all products are subject to design
and/or material change without notice
ISSUED 07/2013 M2013-1402
COPYRIGHT ©2013 SPX Corporation