Download FX3U-CAN USER`S MANUAL
Transcript
5 Introduction of Functions FX3U-CAN User's Manual 5.6 Communication Profile Area 1 The default mapping is to unsigned 16 bit objects. Refer to Subsection 7.1.1 31 ... 16 15 ... 8 7 ... 0 Index Sub-index Length 2 Item Description / set range Sub-index of the mapped Object Length Bit length of the mapped Object Timing chart H0001 H5374 H2102 H3528 6 BFM #20 bit0 H0000 H0001 H5374 H2102 Allocation of Buffer Memories OD data H3528 TPDO 1 Inhibit time 7 H0001 H5374 H2102 Interface and Device Profile (405 mode) TPDO 1 Event timer CAN Bus TPDO 1 5 Introduction of Functions Example 1: Inhibit time = 0, Event time = 0 The BFM data will be copied into the Object dictionary and a PDO will be sent every time when the data are changed and a data exchange is triggered. If the data are not changed, no PDO will be sent if a data exchange is triggered by BFM #20. 4 Wiring The following figures show the relation between Transmit Process Data BFM's (BFM data), BFM #20 bit 0, PDO Inhibit time, PDO Event timer and CAN bus data in NMT state Operational for event driven PDO's. Note that the event and inhibit timer are started every time when PDO transmission is started. BFM data 3 Installation Index of the mapped Object Sub-index Specifications Example: To map unsigned 16bit data of BFM0 to the first 16 bits of TPDO 1, set Index H1A00 Sub-index H01 to HA1000110. This stands for Object Dictionary Index HA100, Sub-index H01 and a data size of 16bit. Index Introduction 4. Object H1A00 to H1A4F Sub-index H01 to H08: TPDO mapping parameter H3528 8 Lift Application Profile (417 Mode) 9 CAN Layer 2 Mode 10 Command Interface 59