Download security and access control (dgp
Transcript
Partition 3: Options Bold = Default setting SECTION [513] : Partition 3 Options Option [1] [2] [3] [4] [5] [6] [7] [8] OFF Partition 3 arms & disarms with Partition 1 N Disabled Partition 3 arms & disarms with Partition 2 N Disabled Switch to Stay Arming (if no delay zone opened) N Disabled Partition 3 arms & disarms with Partition 4 N Disabled Timed Auto-Arming N Disabled “No Movement” Auto-Arming N Disabled Arming method for auto arming N Force Arming Exit Delay termination N Disabled ON N Enabled N Enabled N Enabled N Enabled N Enabled N Enabled N Stay Arming N Enabled SECTION [514] : Partition 3 Options Option [1] [2] [3] [4] [5] [6] [7] [8] Panic 1 (keys [1] and [3]) Panic 2 (keys [4] and [6]) Panic 3 (keys [7] and [9]) Panic 1 alarm type Panic 2 alarm type Panic 3 alarm type Report Disarming Options Future Use OFF N Disabled N Disabled N Disabled N Report Only N Report Only N Report Only N Always report disarming N N/A ON N Enabled N Enabled N Enabled N Audible Alarm N Audible Alarm N Fire Alarm N Report disarming only after alarm N N/A OFF N Disabled N Disabled N Disabled N Disabled N Disabled N Disabled N Disabled ON N Enabled N Enabled N Enabled N Enabled N Enabled N Enabled N Enabled SECTION [515] : Partition 3 Options Option [1] [2] [3] [4] [5] [6] [7] [8] Bell Squawk upon Disarming Bell Squawk upon Arming Bell Squawk upon Auto-Arming Bell Squawk during Exit Delay Bell Squawk during Entry Delay Bell Squawk upon Remote Arming/Disarming Ring Back: bell squawk if disarmed after alarm Ring Back: keypad beeps if disarmed after alarm N Disabled N Enabled SECTION [516]*: Partition 3 Options Option OFF ON [1] One-Touch Regular Arming N Disabled N Enabled [2] One-Touch Stay Arming N Disabled N Enabled [3] One-Touch Instant Arming N Disabled N Enabled [4] One-Touch Force Arming N Disabled N Enabled [5] One-Touch Stay or Instant Disarming N Disabled N Enabled [6] One-Touch Bypass Programming N Disabled N Enabled [7] One-Touch Event Display N Disabled N Enabled [8] No Exit Delay when arming with remote control N Disabled N Enabled * If the keypad is assigned to more than one partition, the feature must be enabled in all the keypad’s partitions. Digiplex DGP-48 - 21 - Programming Guide