Download Refrigerant pipe installation
Transcript
Direction of the pipe when brazing fBrazing the pipe should be done with the pipe headed downward or horizontally. fAvoid brazing with the pipe headed upward. CAUTION t The test liquid used to detect leakage after pipe brazing should be the designated one. The use of the test liquid containing sulfur element may cause pipe corrosion. ENGLISH Cutting or Flaring the pipes fMake sure that you prepared the required tools. - Pipe cutter, reamer, flaring tool and pipe holder, etc. fIf you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe. - There are some examples of correctly and incorrectly cut edges below. Pipe cutter 90° Oblique Rough Burr Pipe fTo prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer. fCarry out flaring work using flaring tool as shown below. [Flaring tool] A York Flaring bar Flaring bar Clutch type Wing nut type Pipe Pipe Flare nut A(mm) Pipe diameter (mm) Flare tool for R-410A clutch type Clutch type Wing nut type ø6.35 0~0.5 1.0~1.5 1.5~2.0 Conventional flare tool ø9.52 0~0.5 1.0~1.5 1.5~2.0 ø12.70 0~0.5 1.0~1.5 1.5~2.0 ø15.88 0~0.5 1.0~1.5 1.5~2.0 fCheck that you flared the pipe correctly. - There are some examples of incorrectly flared pipes below. Correct CAUTION Inclined Damaged Surface Cracked Uneven Thickness t If foreign matters or BURRs are not removed after cutting pipe, refrigerant gas may leak. t If foreign matters enter inside the pipe, the important interior parts of the unit may get damaged or product efficiency will be reduced. So, the direction of pipe should be downward during pipe cutting or flaring. 15 ykTTTtolTptXXZZ]W[hTXXluUGGGX\ YWX\TW]TY`GGG㝘䟸GYaZ^a[W