Download Refrigerant pipe installation

Transcript
Direction of the pipe when brazing
fBrazing the pipe should be done with the pipe headed downward or horizontally.
fAvoid brazing with the pipe headed upward.
CAUTION
t The test liquid used to detect leakage after pipe brazing should be the designated one. The use of the test liquid
containing sulfur element may cause pipe corrosion.
ENGLISH
Cutting or Flaring the pipes
fMake sure that you prepared the required tools.
- Pipe cutter, reamer, flaring tool and pipe holder, etc.
fIf you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe.
- There are some examples of correctly and incorrectly cut edges below.
Pipe cutter
90°
Oblique
Rough
Burr
Pipe
fTo prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.
fCarry out flaring work using flaring tool as shown below.
[Flaring tool]
A
York
Flaring bar
Flaring bar
Clutch type
Wing nut type
Pipe
Pipe
Flare nut
A(mm)
Pipe diameter (mm)
Flare tool for R-410A
clutch type
Clutch type
Wing nut type
ø6.35
0~0.5
1.0~1.5
1.5~2.0
Conventional flare tool
ø9.52
0~0.5
1.0~1.5
1.5~2.0
ø12.70
0~0.5
1.0~1.5
1.5~2.0
ø15.88
0~0.5
1.0~1.5
1.5~2.0
fCheck that you flared the pipe correctly.
- There are some examples of incorrectly flared pipes below.
Correct
CAUTION
Inclined
Damaged Surface
Cracked
Uneven Thickness
t If foreign matters or BURRs are not removed after cutting pipe, refrigerant gas may leak.
t If foreign matters enter inside the pipe, the important interior parts of the unit may get damaged or product
efficiency will be reduced. So, the direction of pipe should be downward during pipe cutting or flaring.
15
ykTTTtolT†pt†XXŽŒ†ZZ]W[hTXX†luU•‹‹GGGX\