Download Refrigerant pipe installation
Transcript
fK11, K12: Changing heating capacity correction table Switch Function K12 ON ON Default ON OFF Default -196 kPa OFF ON Default - 98 kPa OFF OFF Default + 98 kPa ENGLISH K11 ❋ Heating operation increases frequency when current high pressure is higher than target high pressure; vice versa, decreases frequency. When target high pressure is high, the discharge air temperature of an indoor unit will increase but energy consumption will increase as well. ❋ Maintaining factory default status is recommended. However, if you want to reduce energy consumption or you are not satisfied with heating performance, control the operation according to the surrounding environment. As you decrease the target high pressure, energy consumption and noise may decrease but indoor air discharge temperature decreases as well. fK13, K14: Changing current limit option table Switch Function K13 K14 4 HP 5 HP 6 HP ON ON Default Default Default ON OFF Default - 4(A) Default - 2(A) Default - 2(A) OFF ON Default - 6(A) Default - 4(A) Default - 4(A) OFF OFF Default - 8(A) Default - 6(A) Default - 6(A) Classification ø1 ø3 Model Default 4HP RD040MHXE✴ / AM040✴XMDEH 22A 5HP RD050MHXE✴ / AM050✴XMDEH 24A 6HP RD060MHXE✴ / AM060✴XMDEH 32A 4HP RD040MHXG✴ / AM040✴XMDGH 10A 5HP RD050MHXG✴ / AM050✴XMDGH 12A 6HP RD060MHXG✴ / AM060✴XMDGH 12A 43 ykTTTtolTptXXZZ]W[hTXXluUGGG[Z YWX\TW]TY`GGG㝘䟸GYaZ^a[]