Download KMK 8 - SebaKMT
Transcript
5.3.3 Capacitive Balance Measurement Test Procedure Select the CAPACITIVE BALANCE mode and press ENTER and then the measuring arrangement appears: The far endings of the tested pair should be open. Two measuring modes are provided: Sensitive or Protected mode. It is recommended to start the measurement with sensitive mode. When the disturbing voltages overload the indicator a warning appears informing the user that the result can be inaccurate. In that case the measurement should be repeated in protected mode. • Select the proper mode with the MODE (F3) key • Start the measurement with the START/STOP key Having the measurement completed the following results appear: Displayed Test Results • Lx/L relative capacitance rate • Ca-E wire capacitance • Cb-E wire capacitance • ∆C = Ca-E – Cb-E capacitance difference • ∆C% = 2 ∆C / (Ca-E + Cb-E) difference in percents 5-12