Chapter 8. MODBUS COMMUNICATIONS FUNCTIONS • 1-frame end judgment A message end (1-frame end) is determined when a time period specified for each transmission speed has passed during which no character is received. It is considered that 1 frame has ended when the next character is not received before the time-out time shown below passes. However, the time-out time has a fluctuation of ±1 ms from the values in the table below. Set transmission speed (bps) Time-out time 4800 16ms or more 9600 8ms or more 19200 4ms or more 38400 2ms or more ■ Command type There are two command (send message) types as shown below: Command Description ASCII RTU (binary) Read command "03" (sample) 03H (sample) Write command "10" (sample) 10H (sample) ■ Other specifications • Supporting the MODBUS Class 0 • Abnormal termination codes Code 01 Description Command error 02 Address error 03 Data error • Maximum number of communications data words Data count ASCII RTU 03 (READ) 16 16 16 (WRITE) 16 16 • Other For the details of MODBUS specifications, refer to OPEN MODBUS/TCP SPECIFICATION (Release 1.0) by Modicon Inc. 8-6