commissioning
6.2
vacon • 23
Start-up test
Frequency converter application
Choose Fieldbus (Bus/Comm) as the active control place (see Vacon NX User's Manual, Chapter
7.3.3).
Master software
1. Set Control Word value to 0hex.
2. Set Control Word value to 47Fhex.
3. Frequency converter status is RUN
4. Set Reference value to 5000 (=50,00%).
5. The Actual value is 5000 and the frequency converter output frequency is 25,00 Hz
6. Set Control Word value to 477hex.
7. Frequency converter status is STOP
If Status Word bit 3 = 1 Status of frequency converter is FAULT.