Download NX Profibus DP
Transcript
profibus-vacon nx interface 8. vacon • 37 FAULT TRACKING The table below presents the faults related to the Profibus option board. For more information, see also Vacon NX User's Manual, Chapter 9. The Profibus option board status LEDs have been described in more detail in Chapter 4.4. Fault code 37 38 39 40 Fault Possible cause Correcting measures Option board changed. Option board added. Option board removed. Unknown option board. Reset Reset Reset 53 Device change Device added Device removed Device unknown Fieldbus fault The data connection between the Profibus Master and the Profibus option board is broken Check the installation. If installation is correct contact the nearest Vacon distributor. 54 Slot fault Defective option board or slot Check the board and slot. Contact the nearest Vacon distributor. Table 8-1. Profibus option board faults You can define with parameters how the frequency converter shall react to certain faults: Code Parameter Min Max P2.7.22 Response to fieldbus fault 0 P2.7.23 Response to slot fault 0 Unit Step Default ID 3 1 0 733 3 1 0 734 Note 0=No response 1=Warning 2=Fault,stop acc. to 2.4.7 3=Fault,stop by coasting 0=No response 1=Warning 2=Fault,stop acc. to 2.4.7 3=Fault,stop by coasting Table 8-2. Frequency converter responses to faults 24-hour support +358 (0)40 8371 150 • Email: [email protected] 8