Download USER`S MANUAL - Schneider Electric

Transcript
Bulletin 3080IM9601
Analog Input Example
The figure below shows an analog input example. In this example, the analog input has
been configured as follows:
Input Type
Upper Limit
Lower Limit
Offset Voltage
Precision
Units
0–5V
500
100
1 Volt
Units
PSI
The figure below shows the analog input configured as described above.
Circuit Monitor
Reading
( Upper
Limit )
500 PSI
( Lower
)
Limit
100 PSI
5V
1V
Offset
(Voltage
)
Input
Voltage
Input Voltage )
( Maximum
Not User-Definable
The table below shows circuit monitor readings at various input
voltages.
50
Input Voltage
Analog Inputs 2000 Table Reading
0.5 V
N/A (below offset voltage)
1V
100 PSI
2V
200 PSI
2.5 V
250 PSI
5V
500 PSI
5.5 V
500 PSI (above max input voltage)
© 1996 Square D All Rights Reserved