Download 23P-UM001 - Rockwell Automation
Transcript
Chapter 2 Stand Alone Regulator Installation, Wiring and Configuration Figure 6 - AC /DC Voltage Feedback (KP) and Motor Armature Voltage Feedback (KA) Terminal Blocks Bottom View of SAR KPT21 KPT11 D C W V U 1 AC /DC Voltage Feedback (KP) Terminal Block V1 U1 C1 D1 KPT31 1 2 3 4 5 6 7 8 PE 1A1 (C)A1 1A2 (D)A2 2 Motor Armature Voltage Feedback (KA) Terminal Block Table 5 - AC / DC Voltage and Motor Armature Voltage Feedback Terminal Specifications No. Terminal W, V, U 1 1 D, C 1A1, A1, 2 1A2, A2 Wire Size Range Description Maximum Minimum AC Input Feedback (connector KP) DC Output 6.0 mm2 0.2 mm2 Feedback (10 AWG) (24 AWG) (connector KP) Motor Armature Voltage Feedback (connector KA) Recommended Torque 0.7…0.8 N•m (6.2…7.1 lb•in) DC Feedback Fusing Requirements The recommended fuses are: • Bussmann fuse FWP-5A14F (5 A, 700V, Type FWP, 14 x 51mm), or equivalent. Note: The AC voltage feedback inputs on the SAR are fused internally. 22 Rockwell Automation Publication 23P-UM001D-EN-P - July 2012