Download USER MANUAL - BCH Electric Limited
Transcript
11. Monitoring Operating status when a fault occurs Fault type 11.4 Analog Output LED Group Display I/O group I50 I51 Parameter Name [Analog output item output level select] [Analog adjustment] Set Min/Max Factory value range default - 0/3 0 - 10/200 100 Unit % Output item and the level from the AM terminal are selectable and adjustable. I50 : The selected item will be output to Analog output terminal (AM). I50 Analog output 10V item select 0 Output frequency. Max Frequency (F21) 1 Output current 150% of Inverter rated current 2 Output voltage 282 Vac 3 Inverter DC link 400 Vdc voltage I51 : If you want to use Analog output value as a gauge input , the value can be adjustable corresponding to various gauge specifications. AM 0 ~ 10Vdc CM 11-5 SINUS N