S.153 Motor stator R (Motor stator Resistance)
Measurements of the stator resistance of the motor.
This value will be automatically updated, by performing the self tune procedure.
Code
Name
S.150
S.151
S.152
S.153
Motor rated curr
Motor pole pairs
Motor power fact
Motor stator R
[Code] & Function
Default
MIN
MAX
Unit
(*)
(*)
(*)
(*)
(*)
1
0.01
0
(*)
60
1
99.99
A
Variation IPA
0.1
0.01
ohm 0.01
406
407
408
409
(*) parameter value dependent on drive size.
Commands & Referencies
S.200 Cmd source sel (Command source selection)
It defines the use of the main commands START and STOP .
S.200 = 1 START & STOP via terminals
In this configuration the commands are active through the drive terminals.
The motor START command can be performed by applying the specific logic level (high level +15V) , to
the Digital Input 1 (terminal 5), factory set as RUN If this connection is removed, the motor will STOP
with the set ramp time.
For this connection refer to figure 5.3.2.1.
NOTE!
After a cycle of main supply voltage, the drive can be started only according to the settings of P.003
Safety parameter, which allows the Start/Stop commands to respond to Edge or Level sensitive signals
(see chapter 7.6 for more details).
NOTE!
Other configurations for the setting of the "main commands" are described in the chapter
PARAMETERS, section Commands.
Main Commands Logic Control:
"START & STOP"
• The START & STOP function configuration is correlated to other functions and parameters as well as the mode to
REVERSE the motor speed.
These functions allow additional control logic and safety control.
For further information, see chapter PARAMETER, section Commands.
"MOTOR SPEED REVERSAL"
• There are several way to REVERSE the speed direction of the motor. As a default factory setting, the Digital Input
2 (terminal 7) is programmed to this purpose.
All of the frequency references or other variables controlled with digital setting or analog signal, can be
programmed either with positive or negative values. The polarity of the value (Digital or Analog) will determine
the motor rotation direction, without the use of any external HW commands.
Despite the polarity of the reference, the REVERSE command, if programmed on a digital input, will always
reverse the speed direction of the motor.
S.201 Max ref freq (Maximun reference frequency)
It is the threshold for the analog or digital reference and the maximum speed for both directions. This parameter
applies to the sum of the two references value available on the drive.