Download "user manual"
Transcript
Chapter 5 Using the LCD 7. If the channel selected is not configured with the Modbus RTU Slave driver, then Modbus Not Configured is displayed, as shown below. 8. If channel 0 is configured with the Modbus RTU Slave driver with node address 100, the following screen will appear as shown. 9. If channel 2 is configured with the Modbus RTU Slave driver with node address 100, the following screen will appear as shown. 10. The user can configure the node address for either channel by using the Up and Down arrow keys. Once the address is changed, press OK to confirm the change. The following screen appears. 118 Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
Related documents
1762-UM001 - Rockwell Automation
1762-UM001G-EN-P MicroLogix 1200 Programmable Controllers
1769-SG002F-EN-P, Compact I/O Selection Guide
MicroLogix 1400 Programmable Controllers
- NFI: Industrial Automation Training Academy
DG-Bosch-TCT-Attrezzatura Diesel 2013
1761-IN001C-EN-P MicroLogix™ 1000 Programmable Controllers
AB International 1100A User manual
MicroLogix™ 1200 Programmable Controllers
MicroLogix 1400 Programmable Controllers
MicroLogix 1100 Programmable Controllers User Manual
1766-IN001 - Rockwell Automation