Appendix 71/85 The maximum length of a bus segment depends on the baudrate used, see the following table. Baud rate in kBit/s Max. distance in m 9,6 1.200 19,2 1.200 93,75 1.200 187,5 1.000 500 400 1.500 200 3.000 100 6.000 100 12.000 100 Table 59: PROFIBUS Segment Length in Dependence of the Baud Rate The following table contains the most important electrical dsata concerning PROFIBUS certified cable: Parameter Value Impedance 135…165 Ω Capacity < 30 pF/m Loop resistance 110 Ω/km Wire gauge 0,64 mm Table 60: Characteristics of PROFIBUS certified Cable netTAP NT 50 | Gateway Devices DOC091202UM02EN | Revision 2 | English | 2010-09 | Released | Public © Hilscher, 2010