NOTE:
You can not measure the voltage of the
output of the 4 Amp Module if there is
no load attached. When there is no
load, the output will show whatever the
input voltage is, so readings will not
accurately show the state of the module.
NOTE:
Network wires must be in separate
conduit than high voltage lines and must
be at least 16” from parallel running
high voltage lines. If network wires cross
high voltage wires they must cross at
90°.
4.3 4 Amp Module Enclosure
The RAPID 4 Amp Module does not come with its own enclosure. It has been designed
to fit in a standard single gang F Series Scepter brand box or equivalent.
The enclosure chosen for the 4 Amp Module must be a CSA and UL approved
non-metallic box with sizing of at least 4 1/4” X 3 1/2” X 2” with NEMA 4 rating.
IMPORTANT:
Ensure that the enclosure is properly
sealed once the module is coded and
wired.
Improper sealing of the enclosure may
lead to an electrical failure at the
module as a result of moisture damage.
IMPORTANT:
The 4 Amp module enclosure should be
mounted so the module sits vertically,
as in Figure 21, and not horizontally.
Do not mount the module on the ceiling.
When mounted vertically, the module
will be less likely to be affected by
moisture and contaminants present in
the barn.
Figure 21
The module slides in between the lid
mounting screws on the side of the
enclosure.