(4) When the disconnected wiring is reconnected
A normal digital output value is stored in the buffer memory area in the next conversion after recovery from the
disconnection. When the averaging processing has been performed, the normal digital output value is stored in
the buffer memory after the disconnected wiring is reconnected and the averaging process cycle elapses.
Until the normal digital output value is stored in the buffer memory area, the digital output value remains a
specified value in the conversion setting at disconnection detection (such as the down-scale value).
(5) Setting procedure
1.
In "Conversion setting for disconnection detection", set a value to be stored in CH Digital output
value (Un\G11 to Un\G14) at disconnection detection.
Project window
2.
[Intelligent Function Module]
module name
When "3: Optional Value" is set, set "Conversion setting value for disconnection detection".
Item
Conversion setting value for disconnection detection
62
[Parameter]
Setting range
-32768 to 32767