Download HTM 64 Sanitary assemblies

Transcript
HTM 64: Sanitary assemblies
Taps
NOTE: Swan-neck outlets should be avoided, as recommended by Health Facilities Note 30 – ‘Infection control in
the built environment’. Therefore, in existing facilities, when such an outlet has become damaged and is due for
repair, this guidance recommends that it be completely replaced by an appropriate, alternative component described
in this section.
TB H1
Application
Identification
Cleaning/maintenance
Lever-action bib tap, 1⁄2 in, long lever.
Standards
•
BS EN 200.
•
BS 5412.
Description
•
Pair, metal bib taps with metal headwork, shrouded
metal quarter-turn, lever-action top with colour
temperature indicators.
•
Lever parallel to wall when tap closed.
•
Open nozzle and flow straightener with minimal
restriction.
•
Tail with G 1⁄2 in. thread. Inlet for 15 mm O/D
supply pipe.
Options
•
Matching extension piece to give 200 mm between
wall and centre line of discharge.
•
Short-lever pattern (approximately 75 mm).
Suitable for use with sinks and hoppers.
Exposed surfaces smooth and easily cleaned.
TB H2a
Identification
Integral thermostatic hospital pattern bib combination
mixer tap with single lever, single flow, fixed horizontal
nozzle 2 x 1⁄2 in. inlets. Sequential operation.
Standards
Performance to Model Engineering Specification D08 –
‘Thermostatic mixing valves (healthcare premises)’.
Description
•
Integral thermostatic hospital-pattern bib
combination mixer with sequential operation via
single lever through a minimum travel of 120
degrees cold into hot. Single flow, fixed horizontal
nozzle, 2 x 1⁄2 in. inlets.
Note: Spray and aerator outlet should not be used.
TB H1
44
TB H2a