In the Lock Timeout box enter the amount of time in seconds
that the lock will be ‘live’ for once activated by a successful ID
(for example, a five second timeout would give a user five
seconds to access the door after ID recognition before the
door would lock again).
4
In the Type field, select the strike or bolt type that is connected
to the access controller. If a strike is connected, ensure that
the Standard Strike option is chosen.
Only select the Pulse Strike option if told to do so by a member
of the Ringdale technical support team.
If a bolt is connected to the access controller, select the
Standard Bolt option.
5
If a Ringdale brand strike is connected the Logic field will
become active. Select whether the strike is of the Lock Fails
Closed (PTO) type or the Lock Fails Open (PTL) type (this will
be detailed on the strike itself).
6
Click Apply to save the settings and then click on the Operate
Lock tab to display the following page:
This page provides the ability to remotely operate the lock or
to override the current operation settings.
#