Technical Data Page 3/25 DOA 2.1 1.4 Logic Inputs Logic input type Logic input burden Logic input recognition time Independent optically insulated < 10 m Amps per input < 10ms 1.4.1 Supply The logic inputs shall be powered with a DC or AC voltage. 48 – 200 Vdc or 35 – 150 Vac 1.5 Output Relay Characteristic Contact rating Contact relay Make current Carry capacity Rated Voltage Breaking characteristic Breaking capacity AC Breaking capacity DC Operation time Durability Loaded contact Unloaded contact Dry contact Ag CdO Max. 30A and carry for 3s 5A continuous 250Vac 1250 VA resistive 1250 VA inductive (P.F. = 0.5) 220 Vac, 5A (cos ϕ = 0.6) 135 Vdc, 0.3A (L/R = 30 ms) 250 Vdc, 50W resistive or 25W inductive (L/R=40ms) <7ms 10000 operation minimum 100000 operation minimum 45