Programming 5-21 Advanced Setup Group (continued) [Analog Invert] This parameter enables the inverting function for the 0-10 Volt and 4-20mA analog input signal at TB2. Parameter # 84 Parameter Type Read & Write Units Text Factory Default ‘‘Disabled” Settings ‘‘Enabled” ‘‘Disabled” Figure 5.12 Analog Invert Maximum Input Commands [Minimum Freq] Minimum Input Commands [Maximum Freq] Maximum Input Commands [Maximum Freq] Minimum Input Commands [Minimum Freq] [Maximum Frequency] ' Disabled Drive Output Enabled [Minimum Frequency] ' y 0V 4 mA [4-20mA [4 20mA Loss Sel] This parameter p selects the drives reaction to a loss of a 4 20 A signal 4-20mA i l when h the th active ti [Frequency [F S Source]] iis 4 20mA Important: The drive output contacts can be 4-20mA. used to issue an alarm signal by setting [Output 1 Config] or [Output 2 Config] to “alarm”. alarm . Important: Loss of signal is defined as a signal < 3.5 mA or a signal > 20.5 mA. Parameter # 81 Parameter Type Read & Write Units Text y 10 V 20 mA Factory Default ‘‘Stop/Fault” Settings ‘‘Stop/Fault” ‘‘Hold/Alarm” ‘‘Max/Alarm” ‘‘Pre1/Alarm” ‘‘Min/Alarm” Drive Stops and Issues ‘‘Hz Err Fault” (F29) Drive Maintains Last Output Freq and sets an Alarm bit Drive Outputs [Maximum Freq] and sets Alarm bit Drive Outputs [Preset Freq 1] and sets an Alarm bit Drive Outputs [Minimum Freq] and sets an Alarm bit