Download RKS User Manual - Cycle Manager Login
Transcript
Setting Alarm Thresholds 2. Choose 2. Alarm Thresholds and push the ENTER button. Now you'll see the following display: 3. Use the item selectors to select 3. Flow Deviation. Now you'll see the following display: 4. Use the item selectors to set the deviation percentage from expected flow. The controller will raise an alarm if the flow exceeds or falls short of the expected flow with this many percent. If this alarm is activated all running stations will be halted and blacklisted (marked as failed). Any programs that include failed stations will simply skip those stations and run the next one in the program. To clear a station you need to mark it OK on the controller (see Managing station status [110] for instructions.) You can read more about the expected flow in Section C.2.5, “Setting Expected Station Flow” [107]. 5. Push the ENTER button to save your selection. Procedure C.8. Setting the unscheduled flow threshold 1. Turn the mode selector to ADVANCED, use the item selectors to scroll to item number 3. FloGuard, and push the ENTER button. Now you'll see this display: 2. 104 Choose 2. Alarm Thresholds and push the ENTER button.