Download OMRON - Microptic S.L.
Transcript
Section 5-4 Adjustment Level soak The “program pattern” parameter must not be set to OFF. Soak Time • This parameter sets the time for the control operation when using the simple program function. Function Setting range 1 to 9999 Unit min or h Default 1 Setting ■ Related Parameters See Program start, Soak time remain (operation level): Page 123 Wait band (adjustment level): Page 141 Program pattern (initial setting level): Page 151 Soak time unit (advanced function setting level): Page 181 wt-b The “program pattern” parameter must not be set to OFF. Wait Band • This parameter sets the stable band within which the soak time is measured for the simple program function. Function Setting Note Model Controllers with Thermocouple/Resistance Thermometer Multi-inputs Setting range OFF or 0.1 to 999.9 Unit °C or °F (See note.) Controllers with Analog Inputs OFF or 0.01 to 99.99 %FS Default off Set “none” as the unit for Controllers with Analog Inputs. ■ Related Parameters See Program start, Soak time remain (operation level): Page 123 Soak time (adjustment level): Page 141 Program pattern (initial setting level): Page 151 Soak time unit (advanced function setting level): Page 181 141