Download OMRON - Microptic S.L.
Transcript
Section 5-6 Initial Setting Level sl-h sl-l Function SP Upper Limit SP Lower Limit • These parameters set the upper and lower limits of the set points. A set point can be set within the range defined by the upper and lower limit set values in the “SP upper limit” and “SP lower limit” parameters. If these parameters are reset, any set point that is outside of the new range will be forcibly changed to either the upper limit or the lower limit. • When the temperature input type and temperature unit have been changed, the set point upper limit and set point lower limit are forcibly changed to the upper and lower limits of the sensor. • During temperature input, the decimal point position depends on the currently selected sensor, and during analog input it depends on the “decimal point” parameter setting. Controllers with Thermocouple/Resistance Thermometer Multi-inputs Parameters Setting Set point upper limit Set point lower limit Setting range Unit Default Temperature SP lower limit + 1 to Input range upper limit EU 1300 Analog SP lower limit + 1 to scaling upper limit EU 100 Temperature Input range lower limit to SP upper limit − 1 Scaling lower limit to SP upper limit − 1 EU −200 EU 0 Unit Default Analog Controllers with Analog Inputs Parameters Setting range Set point upper limit SP lower limit + 1 to scaling upper EU limit 100 Set point lower limit Scaling lower limit to SP upper limit − 1 0 EU ■ Related Parameters See cntl Input type: Page 146, Temperature unit: Page 148 (initial setting level) PID ON/OFF • This parameter selects 2-PID control or ON/OFF control. • The auto-tuning and self-tuning functions can be used in 2-PID control. Function Setting range pid: 2-PID, onof: ON/OFF Default onof Setting 149