Download - Service, Support
Transcript
Device-specific Safety Instructions Table 3- 3 Proof test part 3 (only required if external sensors are used) Step Action 1 Bypass the safety PLC or take another appropriate action to avoid a false trip. 2 Select analog input test for Analog Temperature using LUI (local user interface). 3 Connect a calibrated current source, e.g. a loop calibrator, to the analog input 0 for temperature. Note: the current measuring instrument used for this test shall provide an accuracy of 0.1 % or better. 4 Apply at least the following currents in succession: 4.0 mA, 20.0 mA, and a current value within this interval to the analog input. The indicated measured values [mA] shall not deviate more than 0.5 % from the applied current. 5 Select analog input test for Analog Pressure using LUI. 6 Connect a calibrated current source, e.g. a loop calibrator to the analog input 1 for pressure. Note: the current measuring instrument used for this test shall provide an accuracy of 0.1 % or better. 7 Apply at least the following currents in succession: 4.0 mA, 20.0 mA, and a current value within this interval to the analog input. The indicated measured values [mA] shall not deviate more than 0.5 % from the applied current. 8 Restore the loop to full operation. 9 Remove the bypass from the safety PLC and restore to normal operation. Table 3- 4 Step Proof test part 4 Action 1 Bypass the safety PLC or take another appropriate action to avoid a false trip. 2 Unlock the LUI using the service password (Security menu). 3 Select analog output test / analog output 0 using LUI. 4 Connect a calibrated current measuring instrument with loop powering capability, e.g. a loop calibrator, to the analog output 0. Note: the current measuring instrument used for this test shall provide an accuracy of 0.1 % or better. 5 Set at least the following currents in succession: 4.0 mA, 20.0 mA, and a current value within this interval to the analog output. The measured current shall not deviate more than 0.5 % from the set current. 6 Select analog output test / analog output 1 using LUI. 7 Connect a calibrated current measuring instrument with loop powering capability, e.g. a loop calibrator, to the analog output 1. Note: the current measuring instrument used for this test shall provide an accuracy of 0.1 % or better. 8 Set at least the following currents in succession: 4.0 mA, 20.0 mA, and a current value within this interval to the analog output. The measured current shall not deviate more than 0.5 % from the set current. 9 Restore the loop to full operation. 10 Remove the bypass from the safety PLC and restore to normal operation. Safety Manual Operating Instructions, 06/2012, A5E03433511-05 19