Download "user manual"
Transcript
5.1 Variable Area (Setting Range) List Address Fourbyte mode 0722 Parameter name Twobyte mode 2711 MV at PV Error Setting (monitor) value Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0) Heating/cooling: H'FFFFFBE6 to H'0000041A (−105.0 to 105.0) Position proportional (Floating or direct setting of position proportional MV OFF): H'FFFFFFFF to H'00000001 (−1 to 1) Position proportional (Closed and direct setting of position proportional MV ON): H'FFFFFFCE to H'0000041A (−5.0 to 105.0) Level Adjustment 0726 2713 MV Change Rate Limit H'00000000 to H'000003E8 (0.0 to 100.0) 072C 2716 Lower Limit Temperature Input Shift Value H'FFFFB1E1 to H'00007E90 (−199.99 to 324.00) 0730 2718 Upper Limit Temperature Input Shift Value H'FFFFB1E1 to H'00007E90 (−199.99 to 324.00) 0734 271A Heater Current 1 Value Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation 0736 271B Heater Burnout Detection 1 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment 0738 271C Leakage Current 1 Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation 073A 271D HS Alarm 1 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment 0746 2723 Temperature Input Shift H'FFFFB1E1 to H'00007E90 (−199.99 to 324.00) 0748 2724 Heater Current 2 Value Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation 074A 2725 Heater Burnout Detection 2 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment 074C 2726 Leakage Current 2 Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation Adjustment 074E 2727 HS Alarm 2 H'00000000 to H'000001F4 (0.0 to 50.0) 0754 272A Wait Band H'00000000 (0): OFF Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0) Analog: H'00000001 to H'0000270F (0.01 to 99.99) 0756 272B Heater Overcurrent Detection 1 H'00000000 to H'000001F4 (0.0 to 50.0) 0758 272C Heater Overcurrent Detection 2 H'00000000 to H'000001F4 (0.0 to 50.0) 075A 272D Fixed SP SP lower limit to SP upper limit 075C 272E Standby Time H’00000000 to H’00009959 (hours, minutes) H’00000000 to H’00009923 (days, hours) 272F Program SP Shift Value H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 2800 Input Digital Filter H'00000000 to H'0000270F (0.0 to 999.9) Advanced function setting 0810 2808 Extraction of Square Root Low-cut Point H'00000000 to H'000003E8 (0.0 to 100.0) Adjustment 0838 281C RSP 0 before Correction Remote SP lower limit to remote SP upper limit 083A 281D RSP 1 before Correction Remote SP lower limit to remote SP upper limit 083C 281E RSP 2 before Correction Remote SP lower limit to remote SP upper limit 083E 281F RSP 3 before Correction Remote SP lower limit to remote SP upper limit 0840 2820 RSP 4 before Correction Remote SP lower limit to remote SP upper limit 0842 2821 RSP 5 before Correction Remote SP lower limit to remote SP upper limit 0844 2822 RSP 6 before Correction Remote SP lower limit to remote SP upper limit 0846 2823 RSP 7 before Correction Remote SP lower limit to remote SP upper limit 0848 2824 RSP 8 before Correction Remote SP lower limit to remote SP upper limit 084A 2825 RSP 9 before Correction Remote SP lower limit to remote SP upper limit 084C 2826 RSP 10 before Correction Remote SP lower limit to remote SP upper limit 084E 2827 RSP Broken-line Correction Value 0 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 0850 2828 RSP Broken-line Correction Value 1 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 0852 2829 RSP Broken-line Correction Value 2 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 0854 282A RSP Broken-line Correction Value 3 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 0856 282B RSP Broken-line Correction Value 4 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 0858 282C RSP Broken-line Correction Value 5 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 085A 282D RSP Broken-line Correction Value 6 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 085C 282E RSP Broken-line Correction Value 7 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 085E 282F RSP Broken-line Correction Value 8 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 0860 2830 RSP Broken-line Correction Value 9 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 0862 2831 RSP Broken-line Correction Value 10 H'FFFFB1E1 to H'00007E90 (−19999 to 32400) 1800 3800 Program Selection H'00000000 to H'00000007 (0 to 7) Com Data for Modbus 075E 0800 Program 5-5