Download E5CN-H E5AN-H E5EN-H Digital Controller - Innovative-IDM
Transcript
SECTION 2 CompoWay/F Communications Procedures ■ Composite Read from Variable Area This service reads in order the contents of specified addresses in the variable area. Service Request PDU CompoWay/F MRC SRC Variable type 0 1 0 4 2 2 2 Read address 4 Bit position 0 0 2 Variable type Read address 2 4 Bit position 0 0 2 Service Response PDU MRC SRC Response Variable Read data code type 0 1 0 4 2 2 4 2 Number of elements ×8 or 4 Variable type 2 Note: Read data Number of elements ×8 or 4 The read data is read together with the variable type in the order specified by the command. (1) Variable Type and Read Start Address For details on variable types and read start addresses, see SECTION 3 Communications Data for CompoWay/F and SYSWAY. (2) Bit Position The E5CN/AN/EN-H does not support bit access. Fixed to “00.” (3) Number of Read Data Items (Variable Type + Read Data) Read data length Number of read data items For double word 20 max. For word 25 max. (4) Response Code Normal Completion Response code 0000 Name Normal completion Description No errors were found. Error Occurred Response code 1002 2-12 Error name Command too short Cause The command is too short.