5.1 Variable Area (Setting Range) List
Address
Fourbyte
mode
0722
Parameter name
Twobyte
mode
2711
MV at PV Error
Setting (monitor) value
Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating/cooling: H'FFFFFBE6 to H'0000041A (−105.0 to 105.0)
Position proportional (Floating or direct setting of position proportional MV OFF): H'FFFFFFFF to H'00000001 (−1 to 1)
Position proportional (Closed and direct setting of position proportional MV ON): H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Level
Adjustment
0726
2713
MV Change Rate Limit
H'00000000 to H'000003E8 (0.0 to 100.0)
072C
2716
Lower Limit Temperature Input Shift Value
H'FFFFB1E1 to H'00007E90 (−199.99 to 324.00)
0730
2718
Upper Limit Temperature Input Shift Value
H'FFFFB1E1 to H'00007E90 (−199.99 to 324.00)
0734
271A
Heater Current 1 Value Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
0736
271B
Heater Burnout Detection 1
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
0738
271C
Leakage Current 1 Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
073A
271D
HS Alarm 1
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
0746
2723
Temperature Input Shift
H'FFFFB1E1 to H'00007E90 (−199.99 to 324.00)
0748
2724
Heater Current 2 Value Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
074A
2725
Heater Burnout Detection 2
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
074C
2726
Leakage Current 2 Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
Adjustment
074E
2727
HS Alarm 2
H'00000000 to H'000001F4 (0.0 to 50.0)
0754
272A
Wait Band
H'00000000 (0): OFF
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
0756
272B
Heater Overcurrent Detection 1
H'00000000 to H'000001F4 (0.0 to 50.0)
0758
272C
Heater Overcurrent Detection 2
H'00000000 to H'000001F4 (0.0 to 50.0)
075A
272D
Fixed SP
SP lower limit to SP upper limit
075C
272E
Standby Time
H’00000000 to H’00009959 (hours, minutes)
H’00000000 to H’00009923 (days, hours)
272F
Program SP Shift Value
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
2800
Input Digital Filter
H'00000000 to H'0000270F (0.0 to 999.9)
Advanced
function
setting
0810
2808
Extraction of Square Root Low-cut Point
H'00000000 to H'000003E8 (0.0 to 100.0)
Adjustment
0838
281C
RSP 0 before Correction
Remote SP lower limit to remote SP upper limit
083A
281D
RSP 1 before Correction
Remote SP lower limit to remote SP upper limit
083C
281E
RSP 2 before Correction
Remote SP lower limit to remote SP upper limit
083E
281F
RSP 3 before Correction
Remote SP lower limit to remote SP upper limit
0840
2820
RSP 4 before Correction
Remote SP lower limit to remote SP upper limit
0842
2821
RSP 5 before Correction
Remote SP lower limit to remote SP upper limit
0844
2822
RSP 6 before Correction
Remote SP lower limit to remote SP upper limit
0846
2823
RSP 7 before Correction
Remote SP lower limit to remote SP upper limit
0848
2824
RSP 8 before Correction
Remote SP lower limit to remote SP upper limit
084A
2825
RSP 9 before Correction
Remote SP lower limit to remote SP upper limit
084C
2826
RSP 10 before Correction
Remote SP lower limit to remote SP upper limit
084E
2827
RSP Broken-line Correction Value 0
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
0850
2828
RSP Broken-line Correction Value 1
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
0852
2829
RSP Broken-line Correction Value 2
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
0854
282A
RSP Broken-line Correction Value 3
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
0856
282B
RSP Broken-line Correction Value 4
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
0858
282C
RSP Broken-line Correction Value 5
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
085A
282D
RSP Broken-line Correction Value 6
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
085C
282E
RSP Broken-line Correction Value 7
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
085E
282F
RSP Broken-line Correction Value 8
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
0860
2830
RSP Broken-line Correction Value 9
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
0862
2831
RSP Broken-line Correction Value 10
H'FFFFB1E1 to H'00007E90 (−19999 to 32400)
1800
3800
Program Selection
H'00000000 to H'00000007 (0 to 7)
Com Data
for Modbus
075E
0800
Program
5-5