15.
H.
Conduit
1.
3.03
Cable distribution rings for inside wiring cable and distribution
cable shall be Dracon Industries #10941-000, 10942-000 or 1094000, size as required.
No more than 6 feet of flexible conduit shall be used in any
conduit run.
a.
Flexible conduit shall not be used in concealed or
inaccessible areas such as interstitial wall spaces or hard lid
ceilings.
b.
Where flexible conduit is used, the conduit fill shall be derated by one trade size.
c.
Flex shall not be used from MPATC or backboard to the
PA/IC rack.
2.
Pull boxes shall not be used in place of conduit bends unless site
conditions do not allow the use of conduits with data sweeps. If
pull boxes are proposed, it must be approved by the Owner.
3.
Where not required elsewhere in District Specification or Code,
pull boxes shall be sized per the BICSI TDMM current Edition,
Chapter 5, Table 5.13.
OWNERS QUALITY ASSURANCE CERTIFICATIONS AND TESTING
A.
Provide all instruments for testing and demonstrate, in presence of the
Owner, that all circuits and wiring test free of shorts and grounds.
B.
Provide test and reception gear to test for specified performance of active
equipment.
C.
Furnish all labor, instruments, appliances, equipment, and materials
necessary to demonstrate to the Owner the installation performs as
required and specified.
D.
Before Substantial Completion, submit test results and related documents
to the IOR.
E.
The Owner reserves the right to perform independent tests of equipment
furnished, to determine whether or not equipment complies with
requirements specified, and to proceed in accordance with the Contract
Documents.