9 Specifications
Electrical
Power supply:
Power consumption:
RFI/EMI protection
Sensor Performance
Gas detected
Sensor element
Range
Stability & resolution
Repeatability
Long term output drift
Response time
Sensor life expectancy 
Sensor coverage
Mounting height
Type of Control
Analog output signal
Operating Environment
Working temperature
Intermitted temperature
Storage temperature
Working humidity
Intermitted humidity
Pressure range
Physical characteristics
Enclosure material
Enclosure color
Protection
Installation
Dimensions (HxWxD)
Cable entry
Wire connection
Wire size
Wire distance
Weight
Approvals/Listings
- Unit rating
- Enclosure
17-28 VDC (polarity protected)
22 mA, (0.6 VA), max.
5.0 W @1 ft. (0.31 m) radiated
Carbon monoxide (CO)
Electrochemical, diffusion
0 – 250 ppm factory set
0 - 200 to 0 – 300 ppm, adjustable via calibration
± 3.0 ppm of reading
± 3.0 % of reading
 0.4% signal loss/month
t90  50 sec.
3-5 year, normal operating environment
5,000 sq.ft., (465 m2), to10,000 sq.ft. (930 m2) under “ideal conditions”
5 to 6 ft. (1.5 to 1.8 m) above floor
Proportional, 4 – 20 mA, load  450 
14 °F to 122 °F (-10 °C to + 50 °C)
-4 °F to 122 °F (-20 °C to 50 °C)
41 °F to 86 °F (5 °C to + 30 °C)
15 to 95% RH non-condensing
0 to 99% RH non-condensing
Atmospheric ±10%
High impact, GW-Plast, IEC 60695-2-12, GWFI-650 °C, fire-retardant
Light gray
NEMA12 (IP 55)
Wall (surface) mounted or single gang electrical box
5.0 x 3.4 x 2.2 in. (127 x 87 x 56 mm)
1 hole for ½ in. conduit for wall (surface) mounting, and 1 hole
on back side of base plate for single gang electrical box mounting
Terminal blocks, screw type for lead wire
Min. 24 AWG (0.25 mm2), max. 14 AWG (2.5 mm2)
Max. loop resist. 500  (= wire resist. + controller input resist.)
0.6 Ibs. ( 0.25 kg )
NRTL Performance Tested & Certified,
Conforms to STD ANSI/UL 2075
City of Los Angeles
CE
VDI 2053, air treatment systems for garages and tunnels
EMV-Compliance 89/336/EWG,
low voltage directives 73/23/EWG
UL Listed, E208470
CSA Certified, E208470
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
UMLC1112I01
Specification subject to change without notice.
Printed in USA 140916